Premier Elite Series Installation Manual
Expander
Expander does not operate at all
Check that the expander is wired correctly from the control
panel (see page 20 for wiring details)
Check the network fuses F3 and F5 and replace if blown*
*Only on 48/88/168
System does not recognise zones
If the expander is on a long cable run, check the voltage
between the + and – terminals at the expander and ensure that
it measures no less than 10.0V
The speaker output does not work
The expander can be configured so that Alarm, Entry, Exit,
Chime tones etc. can be enabled or disabled. Check that the
expander has been programmed correctly (see page 82 for
details)
The speaker volume on the expander is electronically
adjustable. Check the volume is set to the desired level (see
page 82 for details)
Zones
One or more zones show an alarm
Check that the zone is wired correctly (see page 32 for wiring
details)
Communicator
The Communicator will not dial
By default the communicator is disabled, check that the
communicator is enabled (see page 95 for details)
Check that the telephone line has been correctly wired to the
communicator (see page 37 for wiring details)
Check that the telephone numbers are programmed correctly
(see page 91 for details)
Check that the account numbers are programmed correctly (see
page 91 for details)
Check that the dial attempts are not programmed as zero (see
page 91 for details)
Check that the reporting areas have been programmed correctly
(see page 78 for details)
Check that the reporting options have been programmed
correctly (see page 78 for details)
Communicator dials but does not communicate
Check that the telephone numbers are programmed correctly
(see page 94 for details)
Check that the correct protocol is programmed (see page 94 for
details)
INS176-15
Operation
The system will not allow me to arm
Check that there are no outstanding problems (see page 50 for
details)
Check that there are no outstanding alarms that require resetting
Check that the User code has been programmed to allow
arming (see page 126 for details)
Check that the User code has been assigned to the correct
areas (see page 123 for details)
If a 'Local' User code is being used (see page 126 for details)
ensure that the keypad being used is assigned to the correct
area (see page 79 for details)
The system will not allow me to disarm
Check that the User code has been programmed to allow
disarming (see page 126 for details)
Check that the User code has been assigned to the correct
area(s) (see page 123 for details)
If a 'Local' User code is being used (see page 126 for details)
ensure that the keypad being used is assigned to the correct
area (see page 79 for details)
Commissioning and Troubleshooting
49