Premier Elite Series Installation Manual
05 Global Bell Time
When all areas are armed, the system uses the 'Global Bell Delay' and
'Global Bell Duration' timers (see page 69 for details).
Area Bell Time
When all areas are armed, the system uses the 'Area Bell Delay' and
'Area Bell Duration' timers (see page 61 for details).
06 - 24Hr Omit Global
'24-Hour' type zones can be omitted from any keypad.
24Hr Omit Local
Only
keypads
assigned
'24-Hour' type zones can be used to omit the zone.
07 - Remove Omits
When zones have been 'Omitted' by a user, the zones will be
automatically reinstated by the system when the area they are
assigned to is next disarmed.
Leave Omits
When zones have been 'Omitted' by a user, the zones will remain
omitted until the user reinstates them.
08 - Override Com Dly
If an area is 'Fully' armed and an Intruder alarm occurs in that area,
Intruder alarm events (for that area) are reported to the Alarm
Receiving Centre immediately.
Enforce Com Dly
If an area is 'Fully' armed and an Intruder alarm occurs in that area,
Intruder alarm events (for that area) are reported to the Alarm
Receiving Centre after any programmed 'Coms delay' has expired
(see page 61 for details).
09 - NVM is Unlocked
The factory default settings can be reloaded by pressing the Factory
Restart button during power up.
NVM is Locked
The factory default settings cannot be reloaded by pressing the
factory default button during power up.
If the NVM is locked and the Engineer User code has been lost
or forgotten, the PCB will have to be replaced.
10 - User + Engineer
Access to the Engineers Programming mode can only be obtained, if
a User (with the 'Engineer Access' attribute) has authorised engineer
access (see page 126 for details).
Engineer Only
Access to the Engineers Programming menus can be obtained by
just entering the Engineer User code.
11 - Chime Audible
Zones programmed with the 'Chime 2 or 3' attribute will only
generate a Chime tone.
Chime Visible (Default)
Zones programmed with the 'Chime 2 or 3' attribute will generate a
Chime tone. The keypad will also display the number of the zone that
was activated.
12 - Omit Tampers Yes
A user can omit Tamper faults on a zone.
Omit Tampers No
A user cannot omit Tamper faults on a zone.
To comply with EN50131 at Grade 2 & 3 this should be set to
NO.
13 - Online Printing
If a printer is plugged onto the control panel, anything that is logged
in the event log is also printed at the same time.
Offline Printing
If a printer is plugged onto the control panel, nothing will be printed
unless a printout is requested (see page 136 for details).
14 - Hide Act. Fault
If a zone with the 'Activity' attribute is not activated during the 'Activity
Delay' time window, the area that the zone is assigned to can still be
armed. However, this fault will be indicated to the user when they try
to arm the area.
INS176-15
to
the
same
area
as
View Act. Fault
If a zone with the 'Activity' attribute is not activated during the 'Activity
Delay' time window, the area that the zone is assigned to cannot be
armed. This situation can only be overcome by activating the zone.
15 - Hide Exit Errors
If a user tries to arm an area and there are zones activated, the exit
mode will continue (giving a visual and audible indication that there is
a problem).
View Exit Error
If a user tries to arm an area and there are zones activated, the exit
the
mode is suspended until all of the zones are secure.
16 - Enable Code Tampers
24 invalid key presses on a keypad will cause a Code Tamper
condition (see option 17).
No Code Tampers
A Code Tamper condition will never occur when the keys on a
keypad are pressed more than 24 times.
17 - Code Tamper Alarm
A Code Tamper condition will cause a Tamper alarm in the areas that
the keypad is assigned to.
Code Tamper Lockout
A Code Tamper condition will cause the keypad to lockout for the
duration of the keypad lockout timer (see page 69).
Option 16 above must be set to enable code tampers in order
for this option to work.
18 - Areas A-H & I-P
The first 8 areas will be displayed as letters A through to H and the last
8 areas will be displayed as letters I through to P.
Areas 1-8 & I-P
The
first
8
1 through to 8 and the last 8 areas will be displayed as letters I
through to P.
19 - Auto Area Select
When an Engineers code is entered to gain access to the
programming mode, ALL Zones and Tampers are disabled i.e. if any
Tampers, PA, Fire or Medical Alarms are activated - NOTHING WILL
HAPPEN.
Man. Area Select
When an Engineers code is entered to gain access to the
programming mode, the Engineer will have to select which areas are
going to be worked on.
Zones and Tampers are only disabled for the selected areas all
other areas will respond to zone activations and tampers as
normal.
20 - Predictive Text
When in text editing mode, the control panel will automatically select
predictive text.
Manual Text Edit
When in text editing mode, the control panel will automatically select
normal text.
21 - Short = Tamper
The control panel will see a zone that is in the short circuit condition
as a 'Tamper'.
Short = Active
The control panel will see a zone that is in the short circuit condition
as 'Active'.
22 - R/R=Reset Only
When 0V is applied to the control panel R/R input, any areas
programmed for anti-code reset (see page 65 for details) that are in
alarm, will be reset.
R/R=Silence/RST
When 0V is applied to the control panel R/R input any areas
programmed for anti-code reset (see page 65 for details) that are in
alarm, will be silenced. When 0V is applied to the R/R input a second
time, the areas will be reset (this would normally be used when Audio
Verification is required).
areas
will
be
displayed
Global Options
as
numbers
71