Selecting A Location - Fedders HFC1009N2F Installation And Operation Manual

Ductless split air conditioner
Table of Contents

Advertisement

Available languages

Available languages

Before beginning installation, consider the placement of both the
indoor and outdoor units. It is important to correctly measure the
distance the tubing will need to travel between the two units.
Select a location for the outdoor unit
Make sure you do not block the discharge area of the outdoor
unit with plants or debris
Do not install either unit near any source of heat, steam or
flammable gas
Locate the unit in a location where it can be easily maintained
Select a location for the indoor unit
Locate the indoor unit in a place where it will provide cool air
throughout the room
Locate the indoor unit in a place where the unit's airflow will
not be obstructed
The wall that the indoor unit is mounted to must be
structurally sound and able to support the weight of the unit
It is preferable to locate the indoor unit on an outside wall
where there will be access to adequate drainage or a drain
source
Place the unit so that the air filter can be removed easily and
maintenance work can be performed without interference
Maintain minimum distances from walls, ceiling, and floor
illustrated in figure 3 on page 5 of this manual
Tubing Line Length and Refrigerant Charge
Each indoor unit comes with a refrigerant charge that is
sufficient for use with tubing up to 16.4 feet.
If the required length of connecting tubing exceeds 16.4 feet,
add 0.23 oz/ft of refrigerant for each additional foot.
The maximum allowable tubing length between indoor
unit and outdoor unit is 32 feet.
Unit Elevation
If the outdoor unit is placed higher than the indoor unit, an oil
trap should be installed every 12 feet in the suction line.
The maximum allowable elevation between indoor and
outdoor is 16.5 feet.
CAUTION
CAUTION

SELECTING A LOCATION

11 1
Maximum
allowable
tubing length
between indoor
and outdoor
units is 32 feet
Wrap tubing
with tape and
insulation
Outdoor
unit
24VDC
power
Suction line
11 2
Indoor Unit
4
Indoor unit
Wall
Wall bracket
Maximum
allowable
Main
elevation
power
between
indoor unit
and outdoor
unit is
16.5 feet.
Liquid line
Outdoor unit
Roof top
Wall
Oil trap

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents