Icons In The Measured Value And Status Field Of The Channel Display With Relay Output Channels - Dräger REGARD 7000 Instructions For Use Manual

Table of Contents

Advertisement

Control
Icon
Methane %LEL
Methane %LEL
Measurement value
6.14
Icons in the measured value and status field of the
channel display with relay output channels
Icon
12
321s
Gas and unit
5 oo 9
3 oo 5
Common
1234
12 oo 42
Common
Description
An over range, a second alarm, additional alarms
and a warning are pending.
A first alarm, information and a communication
error are pending.
The input channel remains in the inhibit state for
321 s. A second alarm, additional alarms, infor-
mation and multiple faults are pending.
Description
The alarm trigger condition is present, the
output is not active yet because a switching
delay is configured and is active.
The output is configured to an extended
voting alarm, the alarm condition is pending
and the relay coil is activated.
The output is configured to an A8 voting
alarm, the alarm condition is pending and
the relay coil is not activated.
The output is configured to a common fault,
it is in test mode and the relay coil is acti-
vated.
The output is configured to a communica-
tion error (Comfail), the alarm condition is
pending, the relay coil is not activated and
the channel is in the Inhibit state.
The output is configured to an voting warn-
ing, the alarm condition and information are
pending and the relay coil is activated.
The output is configured to common infor-
mation, the alarm condition and a commu-
nication error are pending and the relay coil
is not activated.
The alarm trigger condition is no longer
present, the output is still active because a
shut-down delay is configured and is active.
The output is not activated, a fault and
other special states are pending.