Dräger REGARD 7000 Instructions For Use Manual page 34

Table of Contents

Advertisement

System components
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Lights up green if there is valid communication with the fieldbus-specific
gateway.
Fault display
Lights if there is a module or channel error.
LED
Lights when the module is under power.
Data transfer display
Flashes when the module is communicating.
Power/State
Lights when the module is under power.
LEDs for the application without significance.
State
Lights up when a correctly configured and activated Dräger Gateway Module
is connected.
Does not light up if no Dräger Gateway Module has been found or the config-
uration is not correct.
Bus State (Modbus)
Lights if a fieldbus master is connected and is communicating actively.
Does not light if the fieldbus master is not communicating actively for more
than 1 s.
Bus Power
Lights when the module is under power.
Bus (PROFIBUS)
This LED goes out in the data exchange status.
State (PROFIBUS)
green light: PROFIBUS in data exchange status
flashing green: Gateway waits for PROFIBUS configuration data
flashing green/red: Gateway waits for PROFIBUS parameter data
red light: general PROFIBUS error
Bus State (PROFINET)
off: the gateway starts up
green light: Connection to IO controller present, data exchange active
flashing green: PROFINET initialises. Wait for connection with IO controller
flashing red: PROFINET flash test
Link/Act. P1 (PROFINET)
This LED is lit when the gateway on port 1 (X3 P1) is on a functional network
(link pulses are received) and flickers during network data traffic.
Link/Act. P2 (PROFINET)
This LED is lit when the gateway on port 2 (X3 P2) is on a functional network
(link pulses received) and flickers during network data traffic.