Operation
Parameter
Channel group
level 3
Channel groups
Channel groups can be used for the logical grouping of functionally and/or
geographically linked plant sections, e.g. all transmitters and output elements of a
production hall. Up to 3 hierarchically classified channel group levels can be
formed. Note in this process that defined channel groups are not permitted to
contain sub-groups and channels simultaneously.
7.11.8.2
Device parameter menu
Information on the transmitter can be recorded in this menu.
Parameter
Device name
Device part num-
ber
Device serial num-
ber
Startup inhibit time Time for which the channel is inhibited after switching on the
Detector latching
mode
Description
Allocate channel to a logical group stage 3 (e.g. room 1).
Description
Input device name of the input element connected to the
channel.
Order number of the input element.
Serial number of the input element.
input element power supply voltage. Ensures that no alarms
are triggered during the warm-up phase.
Adjustable range: 0 to 600 s
Behaviour of the digital input on a connected manual or
automatic fire alarm.
Latching: A latching fire alarm is acknowledged by briefly
switching the operational voltage off and on at the relevant
channel.
Non-latching: The state of the connected input element is
processed in accordance with the system configuration. The
supply voltage of the digital input is not shut down.