Supply current of the con-
nected input elements:
Static current through
EOL resistor:
Switching threshold:
Power input:
Power loss:
Deviation with adjustable
time parameters:
Monitoring functions:
Terminal Block:
4.2.4
Relay Module 240 V AC / 240 V AC complex
Output module in 2 types with 8 independent relay outputs each for switching mains
power loads.
The 240 V AC complex type offers more comprehensive configuration options for
switching conditions for a relay contact.
1
2
Max. 400 mA per channel, with assignment of max. 4
inputs.
max. 250 mA per channel, with assignment of 4 to
8 inputs.
Total supply current max. 2 A.
Configurable to 0 mA (wire break detection disabled)
and in the range from 5 to 400 mA.
Configurable in the range
Rising: 3 to 400 mA
Falling: -3 to -400 mA
Accuracy: ±2 % of the measured value
max. 2.1 A
Max. 5 W at 24 V
Max. ±1 %
– wire break detection (0.5 x static current)
– short-circuit detection (loop current < 450 mA)
– total current monitoring (total of loop currents of all
16-pin, DC,
16-pin Res, DC
Relay display
Lights if current is flowing through the relay coil.
Fault display
Lights if there is a module or channel error.
channels > 2000 mA)
O/P 1
O/P 2
O/P 3
1
O/P 4
O/P 5
O/P 6
O/P 7
O/P 8
2
3
4
REGARD 7000
O/P Relay DC
System components