Installation and removal

4.8 Mounting tensile strain relief

4.8
Mounting tensile strain relief
Required tools
• Torx screwdriver, size T10
• Cable ties
We recommend cable ties with a width of 4.8 mm. The maximum width is 7.0 mm. The
length of the cable tie is min. 60 mm.
Installation
Figure 4-6
To mount tensile strain relief on the device, follow the steps below:
1. Bring the gap in the strain relied in line with the gap in the device
2. Screw the strain relief with the supplied screw (tightening torque 0.8 Nm)
Use the specified tool for this.
3. Mount a bus adapter, see section "Mounting bus adapters (Page 52)".
4. Insert the connection plugs into the sockets intended for this on the bus adapter.
5. Use cable ties to secure the cable to the strain relief.
Removal
To remove strain relief from the device, follow the steps below:
1. Release the cable from the strain relief and pull the cable.
2. Remove the bus adapter, see section "Mounting bus adapters (Page 52)".
3. Loosen the screw connection.
4. Remove the strain relief.
54
Mounting tensile strain relief
Operating Instructions, 11/2021, C79000-G8976-C284-15
.
.