Connecting up
5.1 Safety when connecting up
Notes for use in hazardous locations according to ATEX, IECEx, UKEX and CCC Ex
If you use the device under ATEX, IECEx, UKEX or CCC Ex conditions you must also keep to the
following safety instructions in addition to the general safety instructions for protection against
explosion:
Transient overvoltages
Take measures to prevent transient overvoltages of more than 40% of the rated voltage (or
more than 119 V). This is the case if you only operate devices with SELV (safety extra-low
voltage).
Safety notices when using the device according to Hazardous Locations (HazLoc)
If you use the device under HazLoc conditions you must also keep to the following safety notices
in addition to the general safety notices for protection against explosion:
EXPLOSION HAZARD
You may only connect or disconnect cables carrying electricity when the power supply is
switched off or when the device is in an area without inflammable gas concentrations.
EXPLOSION HAZARD
Do not disconnect while circuit is live unless area is known to be non-hazardous.
Further notes
Safety notice for connecting with a LAN ID (Local Area Network)
A LAN or LAN segment with all the interconnected devices should be contained completely in
a single low voltage power distribution in a building. The LAN is designed either for
"Environment A" according to IEEE802.3 or "Environment 0" according to IEC TR 62102.
Do not connect any electrical connectors directly to the telephone network (telephone network
voltage) or a WAN (Wide Area Network).
60
WARNING
WARNING
WARNING
WARNING
Operating Instructions, 11/2021, C79000-G8976-C284-15