[ II Restrictions ]
Pro
ce-
Unit or controller
du-
res
1
Indoor
Main unit
unit
Sub unit
2
LOSSNAY
3
M-NET
Main
remote
remote
controller
controller
Sub
remote
controller
4
Outdoor unit
5
Auxiliary
BC
unit
controller
(main)
BC
controller
(sub)
Address setting method
Address
setting
Setting method
range
IC
01 to 50
Assign the smallest address to
the main unit in the group.
In an R2 system with a sub BC
controller, make the settings for
the indoor units in the following
order.
(i) Indoor unit to be connected
to the main BC controller
(ii) Indoor unit to be connected
to sub BC controller 1
(iii) Indoor unit to be connected
to sub BC controller 2
Make the settings for the indoor
units in the way that the formula
"(i) < (ii) < (iii)" is true.
Assign sequential numbers start-
ing with the address of the main
unit in the same group +1. (Main
unit address +1, main unit ad-
dress +2, main unit address +3,
etc.)
LC
01 to 50
Assign an arbitrary but unique
address to each of these units af-
ter assigning an address to all in-
door units.
RC
101 to
Add 100 to the main unit address
150
in the group
RC
151 to
Add 150 to the main unit address
200
in the group
OC
51 to 100 The sum of the smallest address
of the indoor units in the same
system and 50
BC
52 to 100 Outdoor unit address + 1
BS
Assign an address that equals
the sum of the smallest address
of the indoor units that are con-
nected to the sub BC controller
and 50.
- 48 -
Facto-
Notes
ry set-
ting
Enter the indoor unit
00
group settings on the
system controller
(MELANS).
Port number setting is
required by an R2 sys-
tem.
None of these addresses
00
may overlap any of the
indoor unit addresses.
It is not necessary to
101
set the 100s digit.
To set the address to
200, set it to 00.
To set the address to
00
100, set it to 50.
To set the address to
00
100, set it to 50.
If addresses that are
assigned to the main
BC controller overlap
any of the addresses
that are assigned to
the outdoor units or to
the sub BC controller,
use a different, unused
address within the set-
ting range.
The use of a sub BC
controller requires the
connection of a main
BC controller.