Mitsubishi Electric CITY MULTI PUHY-P108 Service Handbook page 209

Table of Contents

Advertisement

[ VIII Test Run Mode ]
Operation
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected
units
Indoor
No. of units in op-
unit
eration
Operat-
ing condi-
Model
tions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
(No.1/No.2)
Indoor unit
LEV
opening
SC (LEV1)
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Discharge
(TH11/TH12)
Heat exchanger
outlet (TH5)
Outdoor
Accumu-
unit
lator
Temp. of
each sec-
Compressor inlet
tion
Compressor shell
bottom
LEV inlet
Indoor
Heat exchanger
unit
outlet
PUHY-P192TGMU-A
DB/
WB
°C
Unit
-
96
48
m
-
kg
A
V
Hz
400
406
Pulse
MPa
Inlet
Outlet
°C
- 200 -
Outdoor unit model
21.1/-
8.3/6.1
4
4
36
12
96
5
10
45
Hi
22.1
53.9/48.7
208/230
82/60
332
254
400
-
2.89/0.68
76/81
4
1
1
1/1
24/27
39
72
PUHY-P204TGMU-A
21.1/-
8.3/6.1
4
4
54
48
18
5
10
45
Hi
28.1
57.5/52.0
208/230
93/60
384
406
373
-
2.83/0.69
76/79
4
1
1
1/1
26/29
38
72

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents