[ VIII Test Run Mode ]
Operation
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected
units
Indoor
No. of units in op-
unit
eration
Operat-
ing condi-
Model
tions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV
opening
SC (LEV1)
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Discharge
(TH11)
Heat exchanger
outlet (TH5)
Outdoor
Accumu-
unit
lator
Temp. of
each sec-
Compressor inlet
tion
Compressor shell
bottom
LEV inlet
Indoor
Heat exchanger
unit
outlet
PUHY-P108TGMU-A
DB/
WB
°F
Unit
-
48
30
Ft
-
lbs-
oz
A
V
Hz
406
280
Pulse
psi
Inlet
Outlet
°F
- 208 -
Outdoor unit model
70/-
47/43
4
4
24
12
54
16
32
147
Hi
30-12
30.6/27.6
208/230
84
455
254
384
-
392/94
169
34
32
32
36
81
95
162
PUHY-P126TGMU-A
70/-
47/43
4
4
48
24
12
16
32
147
Hi
32-6
36.0/32.5
208/230
93
406
455
254
-
393/97
169
36
30
30
32
88
95
162