Mitsubishi Electric CITY MULTI PUHY-P108 Service Handbook page 213

Table of Contents

Advertisement

[ VIII Test Run Mode ]
Operation
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected
units
Indoor
No. of units in opera-
unit
tion
Operat-
ing condi-
Model
tions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
(No.1/No.2)
Indoor unit
LEV
opening
SC (LEV1)
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Discharge
(TH11/TH12)
Heat exchanger out-
let (TH5)
Accumu-
lator
Outdoor
unit
Compressor inlet
Temp. of
each sec-
Compressor shell
tion
bottom
SC heat exchanger
outlet (TH7)
Bypass outlet (TH8)
LEV inlet
Indoor
Heat exchanger
unit
outlet
PUHY-P144TGMU-A
DB/
WB
°F
Unit
-
72
Ft
-
lbs-
oz
A
V
Hz
324
Pulse
psi
Inlet
Outlet
°F
- 204 -
Outdoor unit model
80/67
95/-
4
4
36
24
12
72
16
32
147
Hi
40-2
43.8/39.6
208/230
103
325
441
261
324
164
422/136
187
113
61
61
73
118
81
52
79
59
PUHY-P168TGMU-A
80/67
95/-
4
4
48
30
18
16
32
147
Hi
47-10
46.1/41.7
208/230
65/60
387
275
362
183
428/125
180/185
106
59
59
70/63
91/108
77
48
75
55

Hide quick links: