[ IX Troubleshooting ]
-
(2) Grouping of units in a system with multiple outdoor units
Error Code
6607
No ACK abnormality
(Contin-
ued)
Error
Error dis-
source ad-
play
dress
Outdoor
M-NET re-
unit
mote con-
(OC)
troller (RC)
MA remote
controller
(MA)
BC control-
M-NET re-
ler
mote con-
(BC)
troller (RC)
MA remote
controller
(MA)
Indoor
M-NET re-
unit
mote con-
(IC)
troller (RC)
Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote controller
indicates the controller which did not provide the response (ACK).
Detection
Cause
method
No ac-
Same cause as that for system with
knowl-
one outdoor unit
edgement
(ACK) at
BC trans-
mission to
OC
No ac-
Same cause as that for system with
knowl-
one outdoor unit
edgement
(ACK) at IC
transmis-
sion to BC
No ac-
(1) Same causes as (1) - (5) for sys-
knowl-
tem with one outdoor unit
edgement
(2) Disconnection or short circuit of
(ACK) at
the transmission line for the out-
RC trans-
door unit on the terminal block
mission to
for centralized control line con-
IC
nection (TB7)
(3) When multiple outdoor units are
connected and the power source
of one of the outdoor units has
been shut off.
(4) The male power supply connec-
tor of the outdoor unit is not con-
nected to the female power
supply switch connector (CN40).
(5) The male power supply connec-
tors on 2 or more outdoor units
are connected to the female
power supply switch connector
(CN40) for centralized control.
If an error occurs, after the unit runs
normally once, the following causes
may be considered.
Total capacity error (7100)
Capacity code error (7101)
Error in the number of con-
nected units (7102)
Address setting error (7105)
- 290 -
Check method and remedy
Same remedy as that for system with one
outdoor unit
Same remedy as that for system with one
outdoor unit
1) Turn off the power sources of the out-
door and indoor units for 5 or more min-
utes, and turn them on again. If the error
is accidental, the will run normally.If not,
check the cause 2).
2) Check the causes of (1) - (5). If the
cause is found, correct it. If no cause is
found, check 3).
3) Check the LED displays for trouble-
shooting on other remote controllers
whether an error occurs.
If an error is found,
-> If an error is found, check the check
code definition, and correct the error.
If no error is found,
-> Indoor unit board failure