[ VIII Test Run Mode ]
Operation
Power supply
Ambient
Indoor
tempera-
Outdoor
ture
No. of connect-
ed units
Indoor
No. of units in
Operat-
unit
operation
ing condi-
tions
Model
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
(No.1 / No.2)
Indoor unit
LEV
opening
BC controller (1/2/3)
High pressure/low pressure
Pressure
BC controller on the liquid
side/Intermediate part
Discharge
(TH11/TH12)
Heat exchanger
outlet (TH5)
Outdoor
Accumu-
unit
lator
Temp. of
each sec-
Compressor
tion
inlet
Compressor
shell bottom
LEV inlet
Indoor
Heat exchanger
unit
outlet
PURY-P192TGMU-A
CMB-P108NU-GA
V
208/230
DB/
WB
8.3/6.1
°C
Unit
-
96
48
m
-
kg
A
53.9/48.7
V
208/230
Hz
597
597
Pulse
110/110/980
2.82/0.70
MPa
2.76/2.76
Inlet
Out-
let
°C
- 220 -
Outdoor unit model
Model name of BC controller
PURY-P204TGMU-A
21.1/-
4
4
36
12
96
5
10
45
Hi
28.2
82/60
555
345
597
76/81
4
1
1
1/1
24/27
39
62
CMB-P108NU-GA
208/230
21.1/-
8.3/6.1
4
4
48
48
24
5
10
45
Hi
29.0
57.5/52.0
208/230
93/60
597
597
695
110/110/1050
2.83/0.69
2.77/2.77
76/79
4
1
1
1/1
26/29
38
62

Hide quick links: