Mitsubishi Electric CITY MULTI PUHY-P108 Service Handbook page 137

Table of Contents

Advertisement

[ VI Refrigerant Circuit ]
Part
Symbols
name
(functions)
Linear ex-
LEV
pansion
(SC coil)
valve
(LEV)
Heater
CH11
CH12
Crankcase
heater
4-way
21S4a
valve
21S4b
Notes
Usage
Adjusts the amount of bypass
flow from the liquid pipe on the
outdoor unit during cooling
TH12 is
Heats the refrigerant in the com-
available
pressor
only on
P168-
P234
models
Changeover between heating
and cooling
P126-
1. Changeover between heating
P234
and cooling
models
2. Controls outdoor unit heat ex-
only
changer capacity
- 128 -
Specifications
DC12V
Opening of a valve driven by a
stepping motor 0-480 pulses
(direct driven type)
Cord heater
AC208/230V
CH11, CH12:
928ohm 57W (230V)
AC208/230V
Dead: cooling cycle
Live: heating cycle
AC208/230V
Dead: cooling cycle
Outdoor unit heat exchanger
capacity at 100%
Live: heating cycle
Outdoor unit heat exchanger
capacity at 50%
or heating cycle
Check
method
Same as
indoor LEV
The resis-
tance val-
ue differs
from that
of the in-
door LEV.
(Refer to
the section
"LEV Trou-
bleshoot-
ing.")
Resis-
tance
check
Continuity
check with
a tester

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents