Mitsubishi Electric CITY MULTI PUHY-P108 Service Handbook page 152

Table of Contents

Advertisement

(2) Compressor INV board
[PUHY/PURY]
Switch
SW1
1
Enabling/disabling the following error
detection functions;
ACCT or DCCT sensor circuit error
(530X Detail No. 115, 116)
ACCT or DCCT sensor failure
(530X Detail No.117,118)
IPM open/Disconnected CNCT2
(530X Detail No. 119)
Detection of erroneous wiring
(530X Detail No.120)
2
3
4
SW2
1
2
3
4
Note1 Except for SW2-1, all are set to OFF at factory shipment. Unless otherwise specified, set the switch to OFF
where indicated by "-," which may be set to a certain setting for a reason.
Note2 Leave SW1-1 to OFF during normal operation. If it is set to ON, errors cannot be detected and the unit may be
damaged.
(3) FAN INV board
[PUHY/PURY]
Switch
SW2
1
2
3
4
Note: Except for SW2-1, all are set to OFF at factory shipment. Unless otherwise specified, set the switch to OFF where
indicated by "-," which may be set to a certain setting for a reason.
Function
Error detec-
tion enabled
-
-
-
Inverter address
-
-
-
Function
Inverter address
-
-
-
- 143 -
Function according to switch
setting
OFF
ON
Error detec-
tion disabled
-
-
-
-
-
-
0
1
-
-
-
-
-
-
Function according to switch
setting
OFF
ON
0
5
-
-
-
-
-
-
[ VII Control ]
Switch setting timing
OFF
ON
Anytime after power on
-
-
-
-
-
-
Always leave it to ON
-
-
-
-
-
-
Switch setting timing
OFF
ON
Always leave it to ON
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents