4. Amount of refrigerant to be added <PURY>
The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units.
The amount necessary for extended pipe (field piping) is not included and must be added on site.
Outdoor unit model
Amount of pre-charged re-
frigerant in the outdoor unit
(kg[lbs-oz])
Outdoor unit model
Amount of pre-charged re-
frigerant in the outdoor unit
(kg[lbs-oz])
(1) Calculation formula
The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])
Amount of added refrigerant (kg) = (0.36 x L
+ (0.11 x L
) + (0.12 x L
5
Amount of added refrigerant (oz) = (390 x L
+ (1.18 x L
' ) + (1.29x L
5
L
: Length of ø28.58[1-1/8"] high-pressure pipe (m)
1
L
: Length of ø25.4[1"] high-pressure pipe (m)
2
L
: Length of ø22.2[7/8"] high-pressure pipe (m)
3
L
: Length of ø19.05[3/4"] high-pressure pipe (m)
4
L
: Length of ø15.88[5/8"] high-pressure pipe (m)
5
L
: Length of ø12.7[1/2"] liquid pipe (m)
6
L
: Length of ø9.52[3/8"] liquid pipe (m)
7
L
: Length of ø6.35[1/4"] liquid pipe (m)
8
, α
' : Refer to the table below.
α
1
1
Total capacity of
connected indoor units
-
30
31
-
60
61
-
126
127
-
180
181
-
234
235
-
264
265
-
366
367
-
468
Round up the calculation result to the nearest 0.01kg. (Example: 15.78g to 15.8kg)
Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz.
(Example: 552.5oz to 556oz or 553oz)
P72
P96
10.5[23-3]
13.5[28-11]
P168
P192
22.0[48-9]
22.0[48-9]
) + (0.31 x L
) + (0.23 x L
1
2
) + (0.06 x L
) + (0.024 x L
6
7
8
' ) + (3.33 x L
1
2
' ) + (0.65 x L
' ) + (0.26 x L
6
7
(kg)
'(oz)
α
α
1
1
1.0
36
1.5
53
2.0
71
2.5
89
3.0
106
4.0
142
5.0
178
6.0
212
- 185 -
P108
P126
13.5[28-11]
16.5[36-7]
P204
P216
22.0[48-9]
22.0[48-9]
) + (0.16 x L
)
3
4
) + α
+ α
1
2
' ) + (2.47 x L
' ) + (1.72 x L
3
4
' ) + α
' + α
'
8
1
2
L
' : Length of ø28.58[1-1/8"] high-pressure pipe [ft]
1
L
' : Length of ø25.4[1"] high-pressure pipe [ft]
2
L
' : Length of ø22.2[7/8"] high-pressure pipe [ft]
3
L
' : Length of ø19.05[3/4"] high-pressure pipe [ft]
4
L
' : Length of ø15.88[5/8"] high-pressure pipe [ft]
5
L
' : Length of ø12.7[1/2"] liquid pipe [ft]
6
L
' : Length of ø9.52[3/8"] liquid pipe [ft]
7
L
' : Length of ø6.35[1/4"] liquid pipe [ft]
8
, α
' : Refer to the table below.
α
2
2
Total number of
sub BC controllers
1
2
[ VIII Test Run Mode ]
P144
16.5[36-7]
P234
22.0[48-9]
' )
(kg)
'(oz)
α
α
2
2
1.0
36
2.0
71