Mitsubishi Electric CITY MULTI PUHY-P108 Service Handbook page 138

Table of Contents

Advertisement

(2) PURY
Symbols
Part
(func-
name
tions)
Compres-
MC1
sor
(Comp1)
MC2
P168-P234
(Comp2)
models only
High
63HS
pressure
sensor
Low
63LS
pressure
sensor
Pressure
63H1
63H2 is
switch
63H2
available
only on
P168-P234
models
Notes
Usage
Adjusts the amount of circulating
refrigerant by adjusting the oper-
ating frequency based on the op-
erating pressure data
Operates to secure a constant
amount of circulating refrigerant
when the load exceeds comp1's
capacity
1. Detects high pressure
2. Regulates frequency and pro-
vides high-pressure protection
1. Detects low pressure
2. Provides low-pressure protec-
tion
1. Detects high pressure
2. Provides high-pressure pro-
tection
- 129 -
[ VI Refrigerant Circuit ]
Specifications
Low-pressure shell scroll
compressor
Wirewound resistance
10°C [50°F] : 0.155ohm
20°C [68°F] : 0.161ohm
30°C [86°F] : 0.167ohm
Low-pressure shell scroll
compressor
Wirewound resistance
10°C [50°F] : 0.467ohm
20°C [68°F] : 0.486ohm
30°C[86°F] : 0.505ohm
Pressure
63HS
0~4.15 MPa [601psi]
Vout 0.5~3.5V
1 2 3
0.071V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=1.38 x Vout [V]-0.69
nector
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
GND (Black)
1
2
Vout (White)
3
Vcc (DC5V) (Red)
Pressure
63LS
0~1.7 MPa [247psi]
Vout 0.5~3.5V
1 2 3
0.173V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=0.566 x Vout [V] - 0.283
nector
Pressure [psi]
=(0.566 x Vout [V] - 0.283) x 145
GND (Black)
1
2
Vout (White)
3
Vcc (DC5V) (Red)
4.15MPa[601psi] OFF setting
Check
method

Hide quick links:

Advertisement

Table of Contents
loading