Events - GEM Q50 eSyStep Operating Instructions Manual

Motorized pinch valve
Hide thumbs Also See for Q50 eSyStep:
Table of Contents

Advertisement

Available languages

Available languages

11.4.36 Analog output
The analog output function can be set with the Analog Output parameter.
Index Sub-
Off-
Access
In-
set
Rights
dex
0xBA
1
0
R/W
2
8
R/W
3
16
R/W
4
32
R/W
Description of parameter values
Index name
Analog output

11.5 Events

The following IO-Link events can be transmitted.
Device Hardware Fault
Motor Unable To Move
Device Temperature Over-Run
Emergency Power
Primary Supply Voltage Under-Run
Potifail Close
Potifail Open
Description – Events
Event
Device Hardware Fault
0x5000
Motor Unable To Move
0x8CE0
www.gemu-group.com
Length
Index name
1 bit
Analog output
2 bits
16 bits
16 bits
Parameter
Direction
Type
Min.
(0.0% to Max)
Max.
Min to 1000
(Min to 100%)
Event
Description
The event occurs when a hard-
ware fault is detected.
The event occurs when the
motor is blocked.
Parameter
Direction
Type
Min.
Max.
Values
0
Specify direction of the set value output.
1
0 = Rise (rising)
1 = Fall (falling)
0
Determine signal output.
1
0 = 0 to 20 mA
2
1 = 4 to 20 mA
2 = 0 to 10 V
0 to Max
Determine minimum value of the output.
Determine maximum value of the output.
Mode
App/Disapp
App/Disapp
App/Disapp
App/Disapp
App/Disapp
App/Disapp
App/Disapp
Possible cause
Fault in valve position detec-
tion.
Parameter can no longer be
read when switching the
device on.
Valve is blocked (for example,
solid stuck in valve).
Valve corroded (rusted in
place).
95 / 108
11 Specific data IO-Link (pin 6)
Type
Default
Boolean
0
uint:8
1
uint:16
0
uint:16
1000
Description
Type
Error
Error
Warning/Error
Warning
Error
Warning
Warning
Troubleshooting
Contact GEMÜ Support
Check valve
Carry out initialization if valve
is OK
Values
0
1
0
1
2
0 to Max
(0.0% to Max)
Min to 1000
(Min to 100%)
Code
0x5000
0x8CE0
0x4210
0x5100
0x5111
0x8CA5
0x8CA4
GEMÜ Q50 eSyStep

Advertisement

Chapters

Table of Contents
loading

Table of Contents