Index name
Force initialization
Control parameters
P amplification
D amplification
Derivative time
Open / close tight
Split range
Stroke limiter
Set value (W) input
Analog output
Parameter
Function
Force during initial-
ization, dependent
on valve used
P component – po-
sitioner
D component – po-
sitioner
Delay constant
Dead band
Permissible system
deviation
Open tight
Sealing function
valve position OPEN
Close tight
Sealing function
valve position
CLOSED
Split start
Set set value start
Split end
Set set value end
Max pos
Stroke limiter valve
position OPEN
Min pos
Stroke limiter valve
position CLOSED
Direction
Set value direction
set value input
Type
Determine signal in-
put
I min
Determine minimum
current input
I max
Determine max-
imum current input
U max
Determine max-
imum current input
Direction
Set value direction
set value output
Type
Determine signal
output
Min.
Determine minimum
signal output
Max
Determine max-
imum signal output
77 / 108
11 Specific data IO-Link (pin 6)
Factory
Setting options
settings
1 ... 6
200
1 ... 200
(0.1 ... 20.0)
10
1 ... 200
(0.1 ... 20.0)
0
0 to 100
(0 to 100 s)
10
1 ... 250
(0.1 ... 25.0 %)
995
800 ... 1000
(80.0 ... 100.0 %)
5
0 ... 200
(0 ... 20.0 %)
0
0 to Split End – 100
(0.0 to Split End –
10.0%)
1000
Split Start + 100 to
1000
(Split Start + 10.0%
to 100.0%)
1000
Min Pos to 1000
(Min Pos to
100.0%)
0
0 to Max Pos
(0.0% to Max Pos)
0
0 → Rise (rising)
1 → Fall (falling)
1
0 → 0 to 20 mA
1 → 4 to 20 mA
2 → 0 to 10 V
35
0 to 40
(0 to 4.0 mA)
205
200 to 220
(20.0 to 22.0 mA)
103
100 to 110
(10.0 to 11.0 V)
0
0 → Rise (rising)
1 → Fall (falling)
1
0 → 0 to 20 mA
1 → 4 to 20 mA
2 → 0 to 10 V
0
0 to Max
(0.0% to Max)
1000
Min to 1000
(Min to 100%)