Mounting, demounting and electric installation
That results in the greatest absolute value of 30.2 V as upper voltage limit. The
lowest absolute value of 18.5 V is the lower voltage limit.
10.5.1 Power routing 230 V
Leads
N conductor:
Use only with
permission of
the operator!
e.g. drives
Overvoltage
category I
PE bars are to be installed preferably on the mounting plate. In case of isolated PE bars,
connect both ends to the mounting plate by means of copper strips with a maximum
length of 20 cm. The cross section of the copper strips has to be at least equal to that of
the incoming mains cable.
Fig. 10-9: Power routing 230 V
DANGER
Connect power supply units generating protective extra-low voltage (24 V) on-
ly to supply voltages designed for these power supply units. Comply with the
overvoltage categories, refer
Do not apply the supply voltage to the protective extra-low voltage.
Bosch Rexroth AG R911403058_Edition 01
Min. 16 mm ² ( green/yellow)
16 mm ² (green/yellow)
6 mm² ( green/yellow)
PE neutral point
Fuses, better: protective motor switches
400V
Transformer
acc. to EN 60742
230V
4 mm ² (green/yellow)
PE
N
230 V power supply
operator terminals
service plug receptacle(s)
Power supply unit
VAP01.1H-W23
024-010-NN
DC 24 V
Danger of lethal injury due to hazardous electric
voltage.
tofig. 10-9 "Power routing 230 V" on page
IndraControl VEP 30.6, VEP 40.6,
VEP 50.6 Embedded Terminals
To the housing of the control cabinet
To the device
All housing parts (functional earth)
16 mm ² (green/yellow)
4 mm ² (green/yellow)
1
U2
PE
4 mm ² (green/yellow)
Length max. 4 m
Overvoltage
category III
Overvoltage
category II
Terminals in
isolated
arrangement
+24 V
0 V
30.