Fujitsu AUXG07KVLA Design & Technical Manual page 134

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

• Auxiliary heater control 1
Operation
Heater on
Heater off
– Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
– All control temperatures will shift by adjusting "Thon".
Tr-Ts ≥ -1°C
Tr-Ts ≥ -10°C
Tr-Ts ≥ -1°C
Tr-Ts ≥ -10°C
Tr-Ts ≥ -1°C
Tr-Ts ≥ -10°C
A
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
Example: When set temperature (Ts) is 22°C (Factory setting),
– and room temperature (Tr) increases above 12°C, signal output is on.
– and room temperature (Tr) increases above 21°C, signal output is off.
– and room temperature (Tr) decreases below 19°C, signal output is on.
– and room temperature (Tr) decreases below 10°C, signal output is off.
11-4. Floor type
Heater is on as shown in following diagram of heating temperature.
• Heater is off as shown in following diagram of heating temperature.
• Other than heating mode
• Error occurred
• Forced thermostat off
• Fan stop protection
Tr-Ts
Off
Tr-Ts (=Thon) < -3°C
On
Tr-Ts < -12°C
Off
Tr-Ts
Off
Tr-Ts (=Thon) < -3°C
On
Tr-Ts < -12°C
Off
Tr-Ts
*
Off
Tr-Ts (=Thon) < -3°C
On
Tr-Ts < -12°C)
Off
Condition
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
- 128 -