11-4. Floor type
PCB
Indoor unit
¢ External input
With using external input function, some functions on this product can be controlled from an external
device.
• "Operation/Stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
 Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit connectors.
*1: The switch can be used on the following condition: DC 12 V to24 V,1 mA to15 mA.
11-4. Floor type
CN 23
P 190
External input
Operation/Stop
Forced stop
Forced thermostat off
Connected unit
Indoor unit PCB
CN 21
CN 15
CN
CN
CN 14
PCB
22
20
External output
Operation status
Error status
Indoor unit fan
operation status
External heater output
- 120 -