Fujitsu ASYG07KMCC Design & Technical Manual

Fujitsu ASYG07KMCC Design & Technical Manual

Wall mounted type air conditioner
Hide thumbs Also See for ASYG07KMCC:
Table of Contents

Advertisement

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
ASYG07KMCC
ASYG09KMCC
ASYG12KMCC
ASYG14KMCC
OUTDOOR
AOYG07KMCC
AOYG09KMCC
AOYG12KMCC
AOYG14KMCC
DR_AS120EF_01
2020.01.10

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ASYG07KMCC

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC OUTDOOR AOYG07KMCC AOYG14KMCC AOYG09KMCC AOYG12KMCC DR_AS120EF_01 2020.01.10...
  • Page 2 • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google Inc. ®...
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Dimensions....................4 2-1. Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC.....4 3. Wiring diagrams ....................6 3-1. Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC.....6 4. Capacity table....................7 4-1. Cooling capacity.......................7 4-2. Heating capacity ......................9 5. Fan performance ..................10 5-1.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............39 1. Specifications....................40 2. Dimensions....................41 2-1. Models: AOYG07KMCC, AOYG09KMCC, and AOYG12KMCC........41 2-2. Model: AOYG14KMCC ....................42 3. Installation space ..................43 3-1. Models: AOYG07KMCC, AOYG09KMCC, AOYG12KMCC, and AOYG14KMCC ..43 4. Refrigerant circuit ..................46 4-1. Models: AOYG07KMCC, AOYG09KMCC, and AOYG12KMCC........46 4-2.
  • Page 5: Part 1. Indoor Unit

    Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC...
  • Page 6: Specifications

    1. Specifications Wall mounted Type Inverter heat pump Model name ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC Power supply 230 V ~ 50 Hz Available voltage range 198—264 V 2.00 2.50 3.40 4.20 Rated Btu/h 6,800 8,500 11,600 14,300 Cooling 0.9—3.0 0.9—3.2 0.9—3.9 0.9—4.4...
  • Page 7 Specifications for Lot10 Model name ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC Cooling Energy efficiency class Heating (Average) Cooling 2.0 (35 °C) 2.5 (35 °C) 3.4 (35 °C) 4.2 (35 °C) Pdesign Heating (Average) 2.3 (-10 °C) 2.4 (-10 °C) 2.5 (-10 °C) 4.0 (-10 °C)
  • Page 8: Dimensions

    2. Dimensions 2-1. Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 4 - 2-1. Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC 2. Dimensions...
  • Page 9 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more The flare connection part should be installed outdoors. - 5 - 2-1. Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC 2. Dimensions...
  • Page 10: Wiring Diagrams

    3. Wiring diagrams 3-1. Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC - 6 - 3-1. Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC 3. Wiring diagrams...
  • Page 11: Capacity Table

    Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: ASYG07KMCC Indoor temperature °CDB °CWB °CDB...
  • Page 12 ¢ Model: ASYG14KMCC Indoor temperature °CDB °CWB °CDB 3.77 3.49 0.67 4.11 3.62 0.66 4.34 3.70 0.66 4.57 3.79 0.65 4.85 3.86 0.65 5.03 3.95 0.65 5.37 4.08 0.64 3.59 3.39 0.88 3.92 3.51 0.88 4.14 3.60 0.87 4.35 3.68 0.87 4.62 3.74...
  • Page 13: Heating Capacity

    4-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: ASYG07KMCC Indoor temperature °CDB °CWB 1.85 0.95 1.83 0.97 1.81 0.98 1.80 1.02 1.78 1.04 2.22 1.00 2.20 1.02 2.17 1.03 2.16 1.07...
  • Page 14: Fan Performance

    5. Fan performance 5-1. Air velocity distributions ¢ Models: ASYG07KMCC, ASYG09KMCC, and ASYG12KMCC Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
  • Page 15 ¢ Model: ASYG14KMCC Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right Unit: m/s Side view Vertical airflow direction louver: Up...
  • Page 16: Airflow

    5-2. Airflow ¢ Model: ASYG07KMCC  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 12 - 5-2. Airflow 5. Fan performance...
  • Page 17 ¢ Model: ASYG09KMCC  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 13 - 5-2. Airflow 5. Fan performance...
  • Page 18 ¢ Model: ASYG12KMCC  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 14 - 5-2. Airflow 5. Fan performance...
  • Page 19 ¢ Model: ASYG14KMCC  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 15 - 5-2. Airflow 5. Fan performance...
  • Page 20: Operation Noise (Sound Pressure)

    6. Operation noise (sound pressure) 6-1. Noise level curve ¢ Model: ASYG07KMCC  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15...
  • Page 21 ¢ Model: ASYG12KMCC  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 22: Sound Level Check Point

    6-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 18 - 6-2. Sound level check point 6. Operation noise (sound pressure)
  • Page 23: Safety Devices

    7. Safety devices Model Type of Protection form protection ASYG07KMCC ASYG09KMCC ASYG12KMCC Circuit Current fuse (PCB*) 250 V, 3.15 A protection °C Activate Fan motor stop Fan motor Thermal protection protection °C Reset Fan motor restart Model Type of Protection form...
  • Page 24: External Input And Output

    8. External input and output With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details. CNB02 —...
  • Page 25 • Circuit diagram example • Contact capacity: DC 24 V or more, Indoor unit 10 mA or more. Communication kit Connected unit control PCB • *: Make the distance from the PCB to Example: Switch Connector the connected unit within 10 m. •...
  • Page 26 • Optional part Part name Model name Exterior External input wire External connect kit UTY-XWZXZ5 Communication kit UTY-TWBXF2 * For operating the external function, the wall mounted type requires the communication kit in addi- tion to the wire (UTY-XWZXZ5). - 22 - 8-1.
  • Page 27: External Output

    8-2. External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device. ¢ Operation status output Air conditioner operation status signal can be output. •...
  • Page 28 ¢ Error status output Air conditioner error status signal can be output. • Circuit diagram example: Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased –...
  • Page 29: Group Connection

    9. Group connection Wiring regulation on the remote controllers in the multi split models are reviewed and allowed for group connection. Example of group connection Indoor unit Indoor unit Outdoor unit Outdoor unit *Exterior of each device shown above might be different from the actual one. NOTES: •...
  • Page 30: Remote Controller Address Setting Procedure For Wireless Remote Controllers

    • Required parts for group connection – Optional part: Indoor unit type Communication kit UTY-TWBXF Wall mounted UTY-XWZXZ5 UTY-TWBXF2 As for the optional parts, refer to Chapter 13-2. "Others" on page 37. – Service part: Wire with connector (Service part no. 9705932012) Wiring example for multiple remote control or group control: Crimping terminal and its insulation cap (Locally purchased)
  • Page 31: Remote Controller

    10. Remote controller 10-1. Wireless remote controller ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button...
  • Page 32 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 33: Function Settings

    11. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 11-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 34 NOTES: • The air conditioner custom code is set to prior to shipment. • The remote controller resets to custom code when the batteries on the remote controller are replaced. If you use a custom code other than code , reset the custom code after replacing the batteries.
  • Page 35 ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function no. Functions Remote controller address setting Filter sign...
  • Page 36 2) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
  • Page 37 4) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 38 7) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 8) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
  • Page 39: 11-2.Custom Code Setting For Wireless Remote Controller

    11-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 40: Accessories

    Operating manual Cloth tape Operating manual Tapping screw (large) (CD-ROM) Installation manual Tapping screw (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder - 36 - 12-1. Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC 12. Accessories...
  • Page 41: Optional Parts

    13. Optional parts 13-1. Controllers Exterior Part name Model name Summary Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wired remote Wire type: Polar 3-wire UTY-RVNYM controller Optional communication kit is necessary for installation. Room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor.
  • Page 42 - 38 - 13-2. Others 13. Optional parts...
  • Page 43: Part 2. Outdoor Unit

    Part 2. OUTDOOR UNIT SINGLE TYPE: AOYG07KMCC AOYG09KMCC AOYG12KMCC AOYG14KMCC...
  • Page 44: Specifications

    1. Specifications Type Inverter heat pump Model name AOYG07KMCC AOYG09KMCC AOYG12KMCC AOYG14KMCC Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current Cooling 1,650 1,650 1,700 1,680 Airflow rate Heating 1,450 1,450 1,470 1,580 Type × Q'ty Propeller fan ×...
  • Page 45: Dimensions

    2. Dimensions 2-1. Models: AOYG07KMCC, AOYG09KMCC, and AOYG12KMCC Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 41 - 2-1. Models: AOYG07KMCC, AOYG09KMCC, and AOYG12KMCC 2.
  • Page 46: Model: Aoyg14Kmcc

    2-2. Model: AOYG14KMCC Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 42 - 2-2. Model: AOYG14KMCC 2. Dimensions...
  • Page 47: Installation Space

    3. Installation space 3-1. Models: AOYG07KMCC, AOYG09KMCC, AOYG12KMCC, and AOYG14KMCC ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 48  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 49  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 50: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Models: AOYG07KMCC, AOYG09KMCC, and AOYG12KMCC Heat exchanger 3-way (INDOOR) valve 2-way Muffler valve 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Room temperature) : Thermistor (Pipe temperature) - 46 -...
  • Page 51: Model: Aoyg14Kmcc

    4-2. Model: AOYG14KMCC Heat exchanger 3-way (INDOOR) valve 2-way Muffler valve Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Room temperature) : Thermistor (Pipe temperature) - 47 - 4-2.
  • Page 52: Wiring Diagrams

    5. Wiring diagrams 5-1. Models: AOYG07KMCC, AOYG09KMCC, AOYG12KMCC, and AOYG14KMCC - 48 - 5-1. Models: AOYG07KMCC, AOYG09KMCC, AOYG12KMCC, and AOYG14KMCC 5. Wiring diagrams...
  • Page 53: Capacity Compensation Rate For Pipe Length And Height Difference

    6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOYG07KMCC and AOYG09KMCC NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 54: Model: Aoyg12Kmcc

    6-2. Model: AOYG12KMCC NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — 0.858 0.868 — — 0.929 0.872 0.882 Indoor unit is higher than outdoor unit *1 — 0.960 0.933 0.876 0.885...
  • Page 55: Additional Charge Calculation

    7. Additional charge calculation 7-1. Models: AOYG07KMCC and AOYG09KMCC Refrigerant type Refrigerant amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge 7-2. Model: AOYG12KMCC Refrigerant type Refrigerant amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m...
  • Page 56: Airflow

    8. Airflow 8-1. Model: AOYG07KMCC  Cooling 1,650  Heating 1,450 8-2. Model: AOYG09KMCC  Cooling 1,650  Heating 1,450 8-3. Model: AOYG12KMCC  Cooling 1,700 1,001  Heating 1,470 - 52 - 8-1. Model: AOYG07KMCC 8. Airflow...
  • Page 57: Model: Aoyg14Kmcc

    8-4. Model: AOYG14KMCC  Cooling 1,680  Heating 1,580 - 53 - 8-4. Model: AOYG14KMCC 8. Airflow...
  • Page 58: Operation Noise (Sound Pressure)

    9. Operation noise (sound pressure) 9-1. Noise level curve ¢ Model: AOYG07KMCC  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 59 ¢ Model: AOYG12KMCC  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz ¢...
  • Page 60: Sound Level Check Point

    9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 56 - 9-2. Sound level check point 9. Operation noise (sound pressure)
  • Page 61: Electrical Characteristics

    10. Electrical characteristics Model name AOYG07KMCC AOYG09KMCC AOYG12KMCC AOYG14KMCC Voltage 230 ~ Power supply Frequency Max operating current *1 Starting current Circuit breaker current Power cable Cross- Wiring sectional spec. *2 area Connection cable *3 Limited wiring length *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 62: Safety Devices

    11. Safety devices Model Type of Protection form protection AOYG07KMCC AOYG09KMCC 250 V, 20 A Circuit protection Current fuse (Main PCB) 250 V, 5 A 100±15 °C Activate Fan motor stop Fan motor Thermal protection protection 95±10 °C Reset Fan motor restart 110 °C Activate Terminal protection...
  • Page 63: Accessories

    12. Accessories 12-1. Models: AOYG07KMCC, AOYG09KMCC, AOYG12KMCC, and AOYG14KMCC Part name Exterior Q’ty Part name Exterior Q’ty Installation manual Drain pipe - 59 - 12-1. Models: AOYG07KMCC, AOYG09KMCC, AOYG12KMCC, and AOYG14KMCC 12. Accessories...

Table of Contents