Fujitsu AUXG07KVLA Design & Technical Manual page 108

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

¢ Details of function
 Control input function
• When function setting is "Operation/Stop" mode 1
Function setting
46—00
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
• When function setting is "Forced stop" mode
Function setting
46—02
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
11-1. Compact cassette, Mini duct, and Slim duct types
External input
Terminal
On
Input
Off
Operation
Indoor unit
Stop
Remote controller
External input
Terminal
On
Input
Off
Forced stop
Normal
Operation
Indoor unit
Stop
Remote controller
Input signal
Off → On
On → Off
On
Input signal
Off → On
On → Off
On
- 102 -
Command
Operation
Stop
Command
Forced stop
Normal
On
On
11. External input and output