Page 2
• Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google Inc. ®...
1. Specifications Cassette Type Inverter heat pump Model name AUXG09KVLA AUXG12KVLA AUXG14KVLA Power supply 230 V ~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V 2.50 3.50 4.30 Rated Btu/h 8,500 11,900 14,700 Cooling 0.90—3.20 0.90—4.40 0.90—5.40...
Page 9
Specifications for ErP Lot10 Model name AUXG09KVLA AUXG12KVLA AUXG14KVLA Cooling Energy efficiency class Heating (Average) Cooling 2.5 (35°C) 3.5 (35°C) 4.3 (35°C) Pdesign Heating (Average) 2.6 (-10°C) 3.4 (-10°C) 3.8 (-10°C) SEER Cooling 6.70 6.60 6.50 kWh/kWh SCOP Heating (Average) 4.40...
Page 10
Cassette Type Inverter heat pump Model name AUXG18KVLA AUXG22KVLA Power supply 230 V ~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V 5.20 6.00 Rated Btu/h 17,700 20,500 Cooling 0.90—5.90 0.90—6.70 Min.—Max. Btu/h 3,100—20,100 3,100—22,900 Capacity 6.00 7.00 Rated...
Page 11
Specifications for ErP Lot10 Model name AUXG18KVLA AUXG22KVLA Cooling Energy efficiency class Heating (Average) Cooling 5.2 (35°C) 6.0 (35°C) Pdesign Heating (Average) 4.4 (-10°C) 4.8 (-10°C) SEER Cooling 6.60 6.60 kWh/kWh SCOP Heating (Average) 4.20 4.30 Annual energy con- kWh/a sumption QHE (Average) 1,466...
Hanging bolt position IR receiver Drain hose View A Ceiling Control Box View B View C a: Ceiling openings Cassette grille (Option [Grid type]) 580 to 610 - 6 - 2-1. Models: AUXG09KVLA, AUXG12KVLA, AUXG14KVLA, AUXG18KVLA, and 2. Dimensions AUXG22KVLA...
2-2. Installation space requirement Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) Standard 2,700 High ceiling 3,000 3-way direction setting: Unit: mm 100 or more* NOTES: •...
Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: AUXG09KVLA Indoor temperature °CDB °CWB °CDB...
5. Fan performance 5-1. Air velocity distributions ¢ Model: AUXG09KVLA (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25...
Page 20
¢ Model: AUXG09KVLA (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s...
Page 21
¢ Model: AUXG12KVLA (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward...
Page 22
¢ Model: AUXG12KVLA (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25...
Page 23
¢ Model: AUXG14KVLA (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward...
Page 24
¢ Model: AUXG14KVLA (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25...
Page 25
¢ Model: AUXG18KVLA (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward...
Page 26
¢ Model: AUXG18KVLA (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25...
Page 27
¢ Model: AUXG22KVLA (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view...
Page 28
¢ Model: AUXG22KVLA (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25...
7. Safety devices Model AUXG09KVLA, AUXG12KVLA, Type of protection Protection form AUXG14KVLA, AUXG18KVLA, and AUXG22KVLA Circuit protection Current fuse (PCB*) 250 V, 5 A 100 ± 10 °C Activate Fan motor stop Fan motor protection Thermal protection program 95 ± 10 °C...
8-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V ± 2 V, Low 0 V. •...
8-3. Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input External output Mode Function setting Terminal CN47 60—00...
8-4. Details of function ¢ Control input function • When function setting is "Operation/Stop" mode 1 Function setting External input Input signal Command Off → On Operation 46—00 Terminal On → Off Stop Input Operation Indoor unit Stop Remote controller NOTES: •...
Page 43
• When function setting is "Operation/Stop" mode 2 Function setting External input Input signal Command Off → On Operation 46—03 Terminal On → Off Stop (R.C. disabled) Input Operation Indoor unit Stop (R.C. disabled) Remote controller NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
Page 44
¢ Indoor unit fan operation status Function setting External output Output signal Command Low → High Fan run 60—10 CN47 High → Low Fan stop Output signal Condition The indoor unit fan is operating. Low → High The fan is stopped or during cold air prevention. During thermostat off when in dry mode operation.
9. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 9-1. Function settings on indoor unit By using some components on the PCB, you can change the function settings. ¢...
Page 46
¢ DIP switch setting • SW100: Remote controller address setting NOTE: Because this setting is normally done automatically when 2-core wired remote con- troller is installed, setting is unnecessary. Multiple indoor units can be operated by using one wired remote controller. Set the unit number of each indoor unit.
9-2. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment. ¢ Setting procedure by using remote controller Remote controller is not attached for this product.
Page 48
2) Ceiling height Select the appropriate ceiling height according to the place of installation. Function number Setting value Setting description Factory setting Standard ♦ High ceiling For the specific height for each setting value, refer to “Installation space” in Chapter 2. "Dimensions"...
Page 49
5) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Page 50
8) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 9) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
Page 51
12) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦ 01—08 (Setting prohibited) Error status Indoor unit fan operation status External heater - 45 -...
11. Optional parts 11-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD Wired remote panel. Backlit LCD enables easy UTY-RNRYZ* controller operation in a dark room. Wire type: Non-polar 2-wire High visibility and easy operation. Room temperature can be accurately Wired remote controlled using the built-in thermo...
Exterior Part name Model name Summary Wireless remote Unit control is performed by wireless UTY-LNTY controller remote controller. NOTE: Available functions may differ by the remote controller. For details, refer to the operation manual. 11-2. Cassette grille Exterior Part name Model name Summary This cassette grille can be installed...
11-3. Others Exterior Part name Model name Summary Use to connect with various peripheral External devices and air conditioner PCB. UTY-XWZXZG connect kit For control output port. Air outlet shutter Installed at the air outlet when 3- UTR-YDZB plate directions mode is performed. By attaching Fresh-air intake kit to the Fresh-air intake indoor unit, it can be taken in fresh air...
1. Specifications Type Inverter heat pump Model name AOYG09KBTB AOYG12KBTB AOYG14KBTB Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current Cooling 1,480 1,580 1,670 Airflow rate Heating 1,410 1,520 1,580 Type × Q'ty Propeller fan × 1 Motor output Cooling Sound pressure level *1...
Page 59
Type Inverter heat pump Model name AOYG18KBTB AOYG22KBTB Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current Cooling 2,160 2,240 Airflow rate Heating 1,830 1,960 Type × Q'ty Propeller fan × 1 Motor output Cooling Sound pressure level *1 dB (A) Heating...
2. Dimensions 2-1. Models: AOYG09KBTB, AOYG12KBTB, and AOYG14KBTB Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 54 - 2-1. Models: AOYG09KBTB, AOYG12KBTB, and AOYG14KBTB 2.
2-2. Models: AOYG18KBTB and AOYG22KBTB Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 55 - 2-2. Models: AOYG18KBTB and AOYG22KBTB 2.
3. Installation space 3-1. Models: AOYG09KBTB, AOYG12KBTB, AOYG14KBTB, AOYG18KBTB, and AOYG22KBTB ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 63
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
Page 64
Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Model: AOYG09KBTB NOTE: Values mentioned in the table are calculated based on the maximum capacity.
6-2. Model: AOYG12KBTB NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — — 0.879 0.851 — — — 0.903 0.894 0.867 Indoor unit is higher than — — 0.964 0.918 0.909 0.881...
6-3. Model: AOYG14KBTB NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — — 0.932 0.930 — — — 0.953 0.950 0.947 Indoor unit is higher than — — 0.983 0.968 0.966 0.962...
6-4. Model: AOYG18KBTB NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — — 0.932 0.930 0.924 — — — 0.953 0.950 0.947 0.941 Indoor unit is higher — — 0.983 0.968 0.966...
6-5. Model: AOYG22KBTB NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — — 0.909 0.909 0.903 — — — 0.953 0.950 0.947 0.941 Indoor unit is higher — — 0.983 0.968 0.966...
10. Electrical characteristics Model name AOYG09KBTB AOYG12KBTB AOYG14KBTB Voltage 230 ~ Power supply Frequency Max operating current *1 10.2 Starting current Circuit breaker current Wiring Power cable spec. Cross-sectional area Connection cable *3 Limited wiring length Model name AOYG18KBTB AOYG22KBTB Voltage 230 ~ Power...
11. Safety devices Model Type of Protection form protection AOYG09KBTB AOYG12KBTB AOYG14KBTB 250 V, 20 A 250 V, 25 A Circuit Current fuse (Main PCB) 250 V, 5 A protection 250 V, 3.15 A 125 ±25 °C 100 ±15 °C Activate Fan motor stop Fan motor stop...