TABLE: SERVICE MENU FUNCTIONS
MENU
FEATURE
1
F / C
3
Fan Delay
4
Range Low
5
Range High
6
Setback Low
7
Setback High
8
Zone Temp Offset
9
Keypad Lockout
10
Fan Program Mode
11
Fan Program Speed
12
System Program Mode
14
Setback Mode Enable
15
Outside Air Damper
17
Minimum Deadband
Adjust
25
Pre-occupancy Purge
30
Cycles Per Hour for Cool
32
Cycles Per Hour for Heat
35
Heat Recovery Rate
36
Cool Recovery Rate
40
Output Min Off Time for
Heat and Cool
41
OA/ RV Output
Confi guration
42
Temp Source (Remote)
43
Pairing Start
45
Intermittent Fan
46
Intermittent Fan On Time
47
Intermittent Fan Off Time
© COPYRIGHT 2009 PECO, INC. ALL RIGHTS RESERVED.
RANGE
STD.MODEL
DEFAULT
0, 1
1
0-99 Sec
0
50-90°F, 10-32°C
50°F
50-90°F, 10-32°C
90°F
50-82°F, 10-28°C
55°F
50-90°F, 10-32°C
90°F
+/- 9°F,
0°F
+/- 4.5°C
0-2
0
1-3
3
1-3
3
0-3
1
0, 1
0
0, 1
0
3-10°F,
3°F
1.5-5°C
0-3 Hours
0 Hours
0-6 CPH
5 CPH
0-12 CPH
3 CPH
0-18°F/Hr, 0-10°C/Hr
5°F/Hr, 3°C/Hr
0-18°F/Hr, 0-10°C/Hr
5°F/Hr, 3°C/Hr
1-10 Minutes
4 Minutes
0-4
0
0, 1
0
0, 1
0
0, 1
0
1-60 Minutes
5 Minutes
1-60 Minutes
25 Minutes
DESCRIPTION / COMMENTS
Sets the temperature display in Fahrenheit (1) or Celsius (0).
The amount of time (in seconds) the lowest available fan speed will run after the thermostat
outputs are disabled.
The lowest selectable temperature setpoint value.
The highest selectable temperature setpoint value.
The temperature setpoint value you want the thermostat to Heat to when the thermostat is in the
Setback mode. 0 represents OFF.
The temperature setpoint value you want the thermostat to Cool to when the thermostat is in the
Setback mode. 0 represents OFF.
Zone Temperature offset adjusts the sensed Zone Temperature reading from the A to D
converter, allowing calibration in the fi eld.
Allows you to choose what the occupant can access. The Service Menu is still available if
Keypad Lockout is ON.
1= Disables all buttons except ▲ and ▼ buttons.
2= Disables all buttons.
0= No keypad lockout.
1= ON= Fan is always on regardless of demand.
2= AUTO= Fan is only on with heating or cooling demand.
3= ON or AUTO= User can choose either selection.
1= HIGH= 1-speed fan (only displays "On Auto" in Fan menu)
2= LOW, HIGH= 2-speed fan
3= LOW, MED, HIGH= 3-speed fan
Allows you to determine what system modes the occupant can select.
0= OFF, AUTO
1= OFF, HEAT, COOL, AUTO
2= OFF, HEAT, COOL
3= AUTO, HEAT, COOL
When ON (1), Setback is shown as an available system mode selection. If Setback mode is
selected, the thermostat will control to the current Setback Heat and Setback Cool setpoints.
0= OFF
1= ON
1= OFF= Cycles; OA output cycles with active heat or cool demand.
0= ON= Continuous; OA output is active anytime the thermostat is out of the OFF mode.
A changeover deadband value prevents short cycling between Heating and Cooling modes. The
value is adjustable to meet various HVAC system requirements.
Defi nes a period of time for the fan to run prior to an occupied area, to circulate fresh air.
0 disables cycling and thermostat becomes an ON/OFF control.
0 disables cycling and thermostat becomes an ON/OFF control.
0 disables ramp recovery, uses step response
0 disables ramp recovery, uses step response
Sets the minimum off time for both heat and cool output.
0= OA/ RV Output is used to control the outside air damper.
1= OA/ RV Output is on when there is a demand for heating.
2= OA/ RV Output is on when there is a demand for cooling.
3= OA/ RV Output is 2nd Stage Heat.
4= OA/ RV Output is 2nd Stage Cool.
0= The temperature will be measured by the thermostat's internal sensor.
1= The temperature will be measured by a remote probe connected to the RW205 receiver.
This item should remain OFF until the installer is ready to perform the wireless connection
process to the RW205 receiver.
0= OFF= The thermostat will not attempt to pair with the RW205 receiver.
1= ON= The thermostat will attempt to pair with the RW205 receiver.
If enable is selected, the lowest speed fan will operate during setback operation.
0= Disable
1= Enable
Defi nes the duration in which low-speed fan will be on. Fan On Time will be activated after Fan
Off Time has passed.
Defi nes the duration in which fan will be off. Fan Off Time will be activated after Fan On Time
has passed.
P/N 69512 3220-3139 REV 0 PAGE 3