P E CO WAVE W IR EL E SS
T W S ER IE S T H ER M O S TATS AN D R W S E R I E S C O N T R O L MOD U L E
F OR P TA C/ P TH P A N D C ERTA I N FA N CO I L S Y S T E M S
HIGHLIGHTS
• Frequency Hopping Spread Spectrum Wireless
• 7 Day Programmable (TW206)
• ASHRAE 90.1, and Title 24 Compliant*
• Occupancy HVAC Control Input
• Controlled Off Saftey Option
• Key Pad Lockout - Partial or Full
• Setback Capability
• Auto/ Heat/ Cool/ Off
• Auto Summer/Winter Changeover Option
• Local or Remote Sensing
• LCD Display with Backlight
• Fahrenheit or Celsius Display
* ASHRAE 90.1 or Title 24 compliance requires
TW206 programmable thermostat + RW205 receiver module
P ECO AU TO MATI O N AND C ONTR OLS
SY S TE M
Reduce Installation, Increase Profits and Comfort
The PECO Wave Wireless System offers a cost-effective alternative to expensive
or difficult rewiring retrofit projects. Unlike built-in controls, the wireless units
can be removed and reinstalled as the building floorplan changes without
rewiring walls.
The PECO Wave Wireless System reduces installation time, offering less
disruption for occupants and decreased contractor labor time and expense.
PECO Wave Wireless System Components
The TW205 wireless thermostat is a base level unit offering affordable basic
features, such as 2 Heat/ 2 Cool, 3-speed fan, and manual or auto changeover.
The TW206 wireless thermostat, featuring Title 24 and ASHRAE 90.1 compliance,
offers full 7 day, 4 event programmability making it ideal for condominiums,
residential care facilities, or any PTAC, PTHP, or fan coil application where
programmability is mandated by code. Additional energy saving features
include range limit adjustment, staged fan, occupancy and setback control.
The RW205 receiver module receives input from the TW series thermostats as
well as any occupancy sensing accessory installed to drive the functions of the
PTAC, PTHP, and certain fan coil applications.

Advertisement

Table of Contents
loading

Summary of Contents for Peco WAVE WIRELESS TW205-206

  • Page 1 F OR P TA C/ P TH P A N D C ERTA I N FA N CO I L S Y S T E M S HIGHLIGHTS Reduce Installation, Increase Profits and Comfort The PECO Wave Wireless System offers a cost-effective alternative to expensive • Frequency Hopping Spread Spectrum Wireless or difficult rewiring retrofit projects. Unlike built-in controls, the wireless units •...
  • Page 2: Technical Specifications

    Division of PECO, Inc. Email: sales@pecomanufacturing.com PO Box 82189, Portland, OR 97282 www.pecomanufacturing.com © Copyright 2009. PECO Inc. All Rights Reserved. P/N LCTWRW0309 PECO is a registered trademark of PECO, Inc. The PECO logo is a trademark and/or service mark of PECO, Inc.
  • Page 3: Installation Instructions

    7-day programming, four time periods per day, and hold/override options. functional and safe. APPLICATIONS AND FEATURES The PECO Wave Wireless System is intended for use in PTAC, PTHP, and On/Off control applications. • System mode selections: Off-Heat-Cool-Auto-Setback SPECIFICATIONS •...
  • Page 4 If you are only attempting to add a SW205 occupancy sensor or SW206 door switch 1. Mount thermostat backplate to the wall using the enclosed mounting screws. Tighten to an existing PECO Wave Wireless System, a 5-second connection process can be screws evenly but do not over tighten.
  • Page 5 1-60 Minutes 25 Minutes Defi nes the duration in which fan will be off. Fan Off Time will be activated after Fan On Time has passed. © COPYRIGHT 2009 PECO, INC. ALL RIGHTS RESERVED. P/N 69512 3220-3139 REV 0 PAGE 3...
  • Page 6: Application Notes

    • If the reversing valve needs to be energized with a demand for cooling, set Service Menu #41 to “2”. Note: When using the PECO Wave Wireless System with systems that use the OA/RV OUTPUT for heating or cooling, the outside air damper operation function is not available.
  • Page 7 The thermostat automatically selects the appropriate Heat or Cool mode depending upon the setpoint (desired temperature) and zone temperature (actual temperature). Turns the system off by disabling all outputs on the RW205. © COPYRIGHT 2009 PECO, INC. ALL RIGHTS RESERVED. P/N 69512 3220-3139 REV 0 PAGE 5...
  • Page 9: The Peco Wave Wireless System

    APPLICATIONS AND FEATURES The PECO Wave Wireless System is intended for use in PTAC, PTHP, and On/Off control applications. • System mode selections include: Off-Heat-Cool-Auto-Setback SPECIFICATIONS •...
  • Page 10 6. Cap off any unused wires or terminate properly according to local building codes. 7. Re-attach the RW205 Front Cover. See Figure 2 for proper confi guration if mounting behind a PTAC wall cutout. © COPYRIGHT 2009 PECO, INC. ALL RIGHTS RESERVED. P/N 69566 3220-2240 REV 0 PAGE 2...
  • Page 11 2. On the thermostat: • Set Service Menu #41 to “0”. Note: When using the PECO Wave Wireless System with systems that use the OA/RV (In this case the OA/RV OUTPUT can be used to control and outside air damper.) OUTPUT for heating or cooling, the outside air damper operation function is not available.