Sensor Operating Modes

Sensor #1
Auto-ON
Auto-ON*
Manual-ON
*
Although this configuration may be selected, it is not recommended.
Visit our website for FAQs: www.wattstopper.com
Sensor #2

Light Fixture

Auto-ON
The load turns ON and OFF automatically
based on occupancy detection by either one
of the sensors. The sensors keep the load
ON until no motion is detected and will use
the time delay of the sensor with the lowest
value. At any time, the light can be turned
ON and OFF using the ON/OFF button of any
one of the sensors. If the load is turned OFF
manually by pressing either one of the ON/
OFF buttons, the unit will enter Presentation
mode.
Manual-ON*
The load can only be turned ON automati-
cally by the sensor set in Auto-ON mode. The
sensors keep the load ON until no motion is
detected and will use the time delay of the
sensor with the lowest value. There is either
a 30 second re-trigger delay for the sensor
set in Manual-ON mode or instant re-trigger
for the sensor set in Auto-ON mode. After
the re-trigger delay elapses, the ON/OFF
button of the sensor set in Manual-ON mode
must be pressed to turn the load back on un-
less the sensor set in Auto-ON mode detects
motion. If the light is turned OFF manualy by
pressing the ON/OFF button set in Auto-ON,
it will enter Presentation mode.
Manual-ON
The occupant must press the ON/OFF button
on either one of the sensors to turn the light
ON. The sensors keep the load ON until no
motion is detected and will use the time de-
lay of the sensor with the lowest value. There
is a 30 second re-trigger delay, meaning the
occupant has 30 seconds to be detected for
the sensor to turn the load back on auto-
matically. After the re-trigger delay elapses,
the ON/OFF button of any one of the sensors
must be pressed to turn the load back ON.