WIRING INSTRUCTIONS

■ TIGHTENING TORQUE
Separable screw terminal wiring screw: 0.5 N·m
Separable screw terminal fixing screw: 0.5 N·m
■ SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.25 to 0.75 mm
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
3 (.12) max.
12 (.47) max.
■ HOW TO REMOVE SEPARABLE SCREW TERMINAL
The terminal block is separable in two pieces. Evenly loos-
en two screws on top and bottom of the terminal block to
separate.
FUNCTIONS
■ OUTPUT AT THE LOSS OF COMMUNICATION
• Output Hold
If the network module is in error, the module holds the sig-
nal at error and stands by until the communication recov-
ers.
• Output set value
If the network module is in error, the module holds the
signal at error or power up and stands by until the com-
munication recovers. The the signal at error or power up is
selectable with PC configurator software (Model: R30CFG)
Not depending on output at the loss of communication set-
ting, when power up the module holds the signal at error or
power up and stands by until the normal data is received.
• Output wire breakdown detection
In the case of wire breakdown, output error is detected.
Then, the ERR LED blinks in red and the flag of error is set
on the PLC etc.
2
3.2 (.13) dia.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
CONFIGURATOR SOFTWARE SETTING
The following parameter items can be set with using PC
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.
■ CHANNEL INDIVIDUAL SETTING
ITEM
SETTING RANGE
Unused setting
CH enabled
CH disabled
Fine zero adjust-
-320.00 – +320.00
ment
(%)
Fine gain adjust-
-3.2000 – +3.2000
ment
Scaled range zero
-32 000 – +32 000
Scaled range span
-32 000 – +32 000
Output range at
-15.00 – +115.00 (%)
Communication
Failure or Power up
■ CHANNEL BATCH SETTING
ITEM
SETTING RANGE
Simulate Output
Normal output
Simulation data
Output at the loss
Hold the output data
of communication
User set data output
R30YS4
DEFAULT
SETTING
CH enabled
0.00 (%)
1.0000
0
10 000
-15.00 (%)
DEFAULT
SETTING
Normal output
Hold the out-
put data
EM-9006 Rev.1 P. 5 / 5