Download Print this page

Terminal Connections - M-system R30YS4 Instruction Manual

Dc current output module

Advertisement

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
■ CONNECTION DIAGRAM
INTERNAL BUS
INTERNAL POWER
• Unused Output Channels
Close across the unused output terminals as shown below.
OUTPUT 1
OUTPUT 2
1
2
11
12
Unused channels left open are equal to the wire break-
down, which turns the red ERR LED blink and sets a
burnout flag at the PLC or the host device.
Unused channels can be specified and set so on the PC
Configurator Software (model: R30CFG) without needing
to short at the field terminals.
25 (.98)
20–M3
SCREW
⑭ ⑤
1
I1
OUTPUT1
11
COM1
2
I2
OUTPUT2
12
COM2
3
I3
OUTPUT3
13
COM3
4
I4
OUTPUT4
14
COM4
OUTPUT 3
OUTPUT 4
3
4
13
14
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
98 (3.86)
R30YS4
EM-9006 Rev.1 P. 4 / 5

Advertisement