Heating water buffer cylinder
Setting a time program
■ The time program for the heating
water buffer cylinder is made up of
time phases. Set an operating status
for each time phase ("Top", "Stand-
ard", "Fixed value", see page 43).
Factory setting:
One time phase from 0:00 to 24:00 h
for every day of the week with operat-
ing status "Standard".
■ You can select up to 8 time phases.
Set the start and end points for each
time phase. Between these time pha-
ses, the heating water buffer cylinder
is not heated; only the frost protection
for the heating water buffer cylinder is
active.
■ You can set the time program individ-
ually.
When setting time programs, note that
your heat pump requires some time to
heat the heating water buffer cylinder
to the required temperature.
■ In the extended menu, you can scan
the current time program under "Infor-
mation" (see page 47).
Extended menu:
1.
2. "System"
3. "Time prog. buffer cyl."
4. Select part of the week or a day.
5. Select a time phase ! to (. The
selected time phase is illustrated by a
white bar on the time chart.
42
6. Set the start and end points for the
relevant time phase. The length of the
white bar on the time chart is adapted
accordingly (see the following exam-
ple).
7. Select the required operating status
(see page 43). The individual oper-
ating status is displayed by bars of dif-
ferent heights on the time chart (see
the following example).
Note
Where several time phases overlap,
the operating status with the highest
bar takes priority.
Example:
■ Time program for Monday ("Mo-Su")
■ Time phase !:
6:00 to 09:00 h: "Standard"
■ Time phase ?:
10:00 to 17:00 h: "Top"
■ Time phase §:
17:00 to 22:00 h: "Fixed value"
!
?
Time prog. buffer cyl.
0
2
4
6
8 10 12 14 16 18 20 22 24
? 10:00 - 17:00 u
§ 17:00 - 22:00 u
Select with
Example:
You want to set the same time program
for every day except Monday:
Select the period "Monday–Sunday"
and set the time program.
§
Mo-Su
Top
Fixed value
(