Central heating/cooling
Changing the heating curve
Heating curve
100 °C
43 °C
35 °C
20
10
0
Slope
Change with
Enabling and blocking active cooling mode
The cooling function must be set by your
heating contractor.
If the cooling capacity with the natural
cooling function (for an explanation see
page 63) is inadequate, the heat pump
control unit can start the active cooling
function.
Constant operation of active cooling
mode results in high electricity consump-
tion. You can enable and block the active
cooling mode individually.
Stopping central heating/cooling
Standard menu
1. "Heating" or "Heating/cooling"
2. Where appropriate, select the heat-
ing/cooling circuit.
3. "Heating program"
4. "Only DHW" (no central heating/cool-
ing, only frost protection for the heat
pump)
or
"Standby mode" (no DHW heating,
no central heating/cooling, only frost
protection for the heat pump)
30
HC1
55 °C
49 °C
-20
-30
-10
1.1
(
(cont.)
Depending on various outside tempera-
tures (shown on the horizontal axis), the
assigned set flow temperatures for the
heating circuit are highlighted in white.
Note
Setting the slope or level too high or too
low will not result in damage to your heat
pump or your heating system.
Extended menu
1.
2. "Heating/cooling"
3. Where appropriate, select the heat-
ing/cooling circuit.
4. "Active cooling mod."
For the separate cooling circuit:
Extended menu
1.
2. "Heating/cooling"
3. "Cooling circuit SKK"
4. "Heating program"
5. "Standby mode" (no DHW heating,
no central cooling, only frost protec-
tion for the heat pump)