PREMTBVC2, PREMTBVC3, and PREMTBVC4

Dimensions
• Height: 4.72 in
• Width: 3.39 in
• Depth: 1.06 in
Power Requirements
• 12 VDC, 2.34W, supplied by IDU
Operating Conditions
• 32 °F - 122 °F
• 0% - 95% R.H. non-condensing
Storage Conditions
• -22 °F - 122 °F
• 0% - 95% R.H. non-condensing
Temperature Sensor
• Local 10 K NTC type 2 thermistor
Temperature Sensor Resolution
• ± 0.2 °F
Temperature Control Accuracy
• ± 0.9 °F @ 70 °F, typical calibrated
Humidity Sensor and Calibration
• Single point calibrated bulk polymer type sensor
Humidity Sensor Precision
• Reading range from 10-90 % R.H. non-condensing,
10 to 20% precision: 10%
20% to 80% precision: 5%
80% to 90% precision: 10%
Humidity Sensor Stability
• Less than 1.0 % yearly (typical drift)
Dehumidification Setpoint Range
• 30% - 95% R.H.
Occ, Stand-By and Unocc Cooling Dual Setpoint Range
• 52 - 99 °F
Occ, Stand-By and Unocc Heating Setpoint Range
• 40 °F - 90 °F