Main Specifications For Ms8350 And Ms8650 - LG MultiSITE MS8000 Series Installation Manual

Room controllers
Hide thumbs Also See for MultiSITE MS8000 Series:
Table of Contents

Advertisement

MAIN SPECIFICATIONS FOR MS8350 AND MS8650

Table 5: Main Specifications Table for MS8350 and MS8650.
Item
Dimensions
Power Requirements
Output Ratings
Operating Conditions
Storage Conditions
Temperature Sensor
Temperature Sensor Resolution
Temperature Control Accuracy
Humidity Sensor and Calibration
Humidity Sensor Precision
Humidity Sensor Stability
Dehumidification Setpoint Range
Occ, Unocc and Standby Cooling Setpoint Range
Occ, Unocc and Standby Heating Setpoint Range
Room and Outdoor Air Temperature Display Range
Proportional Band for Room Temperature Control
Analog Inputs
Binary Inputs
Remote Temperature Sensor Requirements
Wiring Gauges
Shipping Weight
Room Controller Input Power
Usage of the CO
sensor module within the Room Controller draws additional power. It is recommended when using the CO
2
transformer be capable to accommodate the additional power consumption. Room Controller power consumption of 12 VA and input voltage range of
24 - 28 VAC is required.
22
Input: 24 - 28 Vac, 50 / 60 Hz (with CO
Analog: 0 - 10 Vdc in 2 kilo-ohm resistance minimum load (maximum 5 mA);
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Description
4.72 in. (H) x 3.38 in. (W) x 1 in. (D) (12cm x 8.6cm x 2.5cm)
Input: 24 Vac ±15%, 50 / 60 Hz
Device consumption: up to 12 Va
Transformer maximum rating: 100 Va, 4.17 A
Relay rating: 28 Vac, 50 / 60 Hz, 1.0 Amp., in-rush = 3.0
Amps; pins 1, 2, 3, 4, 5, 8, 9
Digital optomos output rating: 28 Vac, 50 / 60 Hz,
0.3 Amp., in-rush = 1.5 Amps; pins 9, 10, 11, 12
pins 9, 10, 11, 12
32°F to 122°F (0°C to 50°C)
0% to 75% R.H. non-condensing
-22 °F to +122°F (-30°C to +50°C)
0% to 75% R.H. non-condensing
Local 10 K NTC type 2 thermistor
± 0.2°F (± 0.1°C)
± 0.9°F @ 70 °F (±0.5°C @ 21°C) typical calibrated
Single point calibrated bulk polymer type sensor
Reading range from 10-90% R.H. non-condensing
10% to 20% precision: 10%
20% to 80% precision: 5%
80% to 90% precision: 10%
Less than 1.0% yearly (typical drift)
30% to 95% R.H.
54°F to 100°F (12.0°C to 37.5°C)
40°F to 90°F (4.5°C to 32°C)
-40°F to +122°F (-40°C to +50°C)
Cooling and Heating: Default: 3.2°F (1.8°C)
Modulating 0-10 Vdc across UI19 to Common
Dry contact across terminals UI16, UI17 and UI19 to Common
10 K NTC Type 2 thermistor
Power supply: 18 gauge or larger,
Communications: 24 gauge or larger
0.75 lb. (0.34 kg)
sensor module; see note below)
2
sensor module, the site
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multisite ms8650Multisite ms8350

Table of Contents