Installation location and position

Choosing the loc-
Please note the following criteria when choosing a location for the inverter:
ation of the in-
verter
When installing the inverter on the outer walls of cattle sheds, it is important to keep a
minimum clearance of 2 m between all sides of the inverter and air vents and building
openings.
The following surfaces are permissible for installation:
-
-
-
-
Walls (corrugated metal walls [mounting rails], brick walls, concrete walls, or oth-
er non-flammable surfaces sufficiently capable of bearing loads)
Poles (installed using mounting rails, behind the solar modules directly on the PV
mounting system)
Flat roofs (if this is for a film roof, make sure that the films comply with the fire
protection requirements and are not highly flammable. Ensure compliance with
the national provisions.)
Covered car park roofs (no overhead installation)
The inverter is suitable for indoor installation.
The inverter is suitable for outdoor installation.
Because of its IP 66 protection class, the inverter is resistant to water
jets from any direction and can also be used in damp environments.
In order to minimise the heating up of the inverter, do not expose it to
direct insolation. The inverter should be installed in a protected loca-
tion, for example, near the solar modules or under an overhanging
roof.
Only install on a solid, non-flammable
surface.
Max. ambient temperatures:
-25 °C – +60 °C
Relative humidity:
0-100%
If the inverter is installed in a switch cab-
inet or similar enclosed space, ensure
sufficient heat dissipation with forced-air
ventilation.
For detailed information on the dimen-
sions of the inverter, see chapter
us Symo GEN24 3-5 kW
Froni-
on page 141.