Strip the insulation on the single conduct-
ors by 12 mm and secure to the corres-
ponding slot of the terminal on the PC
board with a torque of 1.2 - 1.5 Nm.
IMPORTANT!
The cable cross-section must be selected
according to the specifications for the re-
spective inverter power category (see
chapter
Permitted cables
Push the DC push-in terminals into the
corresponding slot until there is an audible
click.
Re-insert the connection area divider.
* Lay the ground conductor in the integ-
rated cable duct.
IMPORTANT!
When inserting the connection area di-
vider, be careful not to kink, pinch, crush
or otherwise damage the ground conduct-
or.
on page 45).