Protection Parameters - Sungrow SG125HV-30 User Manual

Pv grid-connected
Table of Contents

Advertisement

9 iSolarCloud APP
PID control parameter
Parameter
PID
Recovery(Night)
Anti-PID(Day)
PID alarm clearing
 After the PID Recovery(Night) / Anti-PID(Day) function is enabled,
the fault indicator on the inverter main panel turns green.
 The PID night recovery function and the PID day protection function
cannot be enabled at the same time.

9.9.5 Protection Parameters

Click the "
related parameters as shown in the following figure.
User can only check the parameter in this interface. The default
values of the protection parameters have been preset as per grid
code of corresponding countries.
To set the protection parameter, please contact SUNGROW to
acquire advanced password.
86
Fig. 9-17 PID control parameters
Description
Set enabling/disabling of the PID night recovery
function. PID night recovery functions between 22:00
pm and 6:00 am by default.
Set enabling/disabling of the PID day protection
function. PID day protection functions only when the
inverter is in grid-connected state.
If ISO impedance abnormality or PID function exception
is detected during running of the PID function, the
inverter reports a PID false alarm and reminds the user
to take corresponding measures. After processing, the
alarm information can be cleared via the function.
" to check the protection parameter and set the
User Manual

Advertisement

Table of Contents
loading

Table of Contents