Commissioning The System With The Commissioning Assistant - Viessmann Vitodens 222-F Installation And Service Instructions For Contractors

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Commissioning the system with the commissioning assistant

Commissioning assistant
Fig. 25
Menu point
"Language"
"Date and time"
"Control unit"
"Building type"
"Filling and venting"
"Gas type"
32
Settings and explanations
"Weather-compensated"
Delivered condition
"Constant"
The control unit can be switched to constant operation (not Vitodens 3xx) if the
system configuration makes this necessary. Not all the described settings are
available in this operating mode.
Note
With each change, all the settings revert to the factory settings.
"Detached house"
One shared holiday program and time program for DHW heating
"Apartment building"
Holiday program and time program for DHW heating can be set separately
See chapters "Filling the heating system" and "Venting the heating system".
Only when operating with LPG: See chapter "Converting the gas type".
To convert the gas type, enter password "9".
1. Turn on the ON/OFF switch on the control unit.
The commissioning assistant starts automatically.
2. Optional settings and functions for commissioning
are listed in the following table.
Note
The optional settings and functions depend on the
type of appliance.
3. When all the required commissioning steps have
been performed, tap "Next".
A safety instruction is shown on the display.
4. After successfully reviewing the safety instruction,
tap "Yes" to confirm.
This initiates an automatic flue gas temperature
sensor test.
The display shows: "Testing, flue gas tempera-
ture sensor" and "Enabled".
If the flue gas temperature sensor is not positioned
correctly, fault message A3 appears on the display.
For further details regarding the flue gas tempera-
ture sensor test, see Maintenance.
5. If fault message A3 appears, reposition the flue
gas temperature sensor in the flue gas connection.
Note
The burner remains blocked until the test has been
passed.
6. When the fault has been remedied, turn the
ON/OFF switch off and then back on again.
Confirm the commissioning assistant with "Next".