Checking The Boiler Water Temperature Sensor, Cylinder Temperature Sensor Or Flow Temperature Sensor Of Low Loss Header - Viessmann Vitodens 222-F Installation And Service Instructions For Contractors

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Maintenance
(cont.)
200
100
80
60
40
20
10
8
6
-20 -10
0
10 20 30
Temperature in °C
Fig. 57
Sensor type: NTC 10 k
Checking the boiler water temperature sensor, cylinder temperature sensor or flow temperature
sensor of low loss header
A
5
Fig. 58
98
Ω
X3
1. Pull plug "X3" from the control unit.
2. Test the resistance of the outside temperature sen-
sor across terminals "X3.1" and "X3.2" on the dis-
connected plug and compare it with the curve.
3. Where actual values deviate severely from the
curve values, disconnect the wires at the sensor
and repeat the test on the sensor itself.
4. Depending on the result, replace the lead or the
outside temperature sensor.