Viessmann Vitodens 222-F Installation And Service Instructions For Contractors page 92

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault code dis-
System characteristics
played
CD
Control mode
CF
Control mode
No communication via LON.
D4
Control mode
Burner is operating with a
limited modulation range.
D5
Burner in a fault state
D6
Control mode
D7
Control mode
D8
Control mode
DA
Control mode without room
influence
DB
Control mode without room
influence
DC
Control mode without room
influence
DD
Control mode without room
influence
DE
Control mode without room
influence
DF
Control mode without room
influence
E0
Control mode
E2
Burner in a fault state
E3
Burner in a fault state
E4
Burner blocked
E5
Burner blocked
E6
Burner blocked
92
Cause
Communication error,
Vitocom 100
Communication error,
LON communication mod-
ule
No air flow detected in fan
unit.
Fan blocked
Input DE1 at EA1 exten-
sion reports a fault.
Input DE2 at EA1 exten-
sion reports a fault.
Input DE3 at EA1 exten-
sion reports a fault.
Short circuit, room tem-
perature sensor, heating
circuit 1 (without mixer)
Short circuit, room tem-
perature sensor, heating
circuit 2 (with mixer)
Short circuit, room tem-
perature sensor, heating
circuit 3 (with mixer)
Lead break, room temper-
ature sensor, heating cir-
cuit 1 (without mixer)
Lead break, room temper-
ature sensor, heating cir-
cuit 2 (with mixer)
Lead break, room temper-
ature sensor, heating cir-
cuit 3 (with mixer)
External LON subscriber
error
No calibration as flow rate
too low
Heat transfer too low dur-
ing calibration.
Temperature limiter has
shut down.
24 V power supply fault
Flame amplifier fault
System pressure too low
Measures
Check connections and
Vitocom 100 (see separate installa-
tion and service instructions).
Without Vitocom 100: set code
"95:0" in the "General"/1 group.
Check LON communication mod-
ule and replace if required.
If no LON communication module
is installed, set code "76:0" in the
"General"/1 group.
Check the mass flow sensor at the
fan unit. Check the flue system for
flue gas back pressure.
Press reset button R.
Check free movement of the impel-
ler. Replace the fan unit if required.
Remedy fault at affected appliance.
Remedy fault at affected appliance.
Remedy fault at affected appliance.
Check room temperature sensor,
heating circuit 1.
Check room temperature sensor,
heating circuit 2.
Check room temperature sensor,
heating circuit 3.
Check room temperature sensor,
heating circuit 1 and remote control
configuration (see page 113).
Check room temperature sensor,
heating circuit 2 and remote control
configuration (see page 113).
Check room temperature sensor,
heating circuit 3 and remote control
configuration (see page 113).
Check connections and LON sub-
scribers.
Ensure adequate heat transfer.
Press reset button R.
Ensure adequate heat transfer.
Press reset button R.
Replace control unit.
Replace control unit.
Top up with water.