Boiler; Dhw - Viessmann Vitodens 222-F Installation And Service Instructions For Contractors

Gas condensing storage combi boiler natural gas and lpg version
Table of Contents

Advertisement

General
(cont.)
"Operation enabled/disabled"
Setting
Everything operable
Everything disabled apart from emissions
test function
Default display and emissions test function
operable
"Set flow temperature for external demand"
Setting
70 °C
... °C

Boiler

Note
Parameter values in bold are factory settings.
"Interval in burner hours until the next service"
Setting
None
... 00 h
"Interval until the next service"
Setting
No time interval
... Months
"Service display"
Setting
No service display
Service is shown on the display (address is
automatically set and must be manually re-
set after a service)
"Filling function / venting function"
Setting
Function disabled
Venting function enabled
Filling function enabled

DHW

Note
Parameter values in bold are factory settings.
Explanations
8F:0
Controls on the display
8F:1
8F:2
Explanations
9B:70
9B:0 to
Adjustable from 0 to 127 °C
9B:127
Limited by boiler-specific parameters
Explanations
21:0
No service interval set
21:1 to
The number of hours run before the burner should be
21:100
serviced is adjustable from 100 to 10,000 h
1 step
100 h
Explanations
23:0
No time interval selected for service
23:1 to
The number of months until the next service is adjust-
23:24
able from 1 to 24
Explanations
24:0
24:1
Displayed only if parameter setting 21 or 23 > 0
Explanations
2F:0
2F:1
2F:2
Parameter level 1
57