Redox scaling

Output scaling 
Menu item
4mA [mV]
20mA [mV]
Damping [s]
The minimum span is 200.
Examples:
mV scaling  from -1000 - 1000.
If there is 12 mA , the mV will be: 
mV = 1000 -((1000 - (-1000))/(20mA-4mA))*(20mA-12mA)
pHix Link software /Main configuration
Option
-1000 - 800
-800  - 1000
0 - 3600
pHix® Compact V3. NG (next generation)
Default 
Description
mV value represented  by
-1000
4mA
mV value represented  by
1000
20mA
Set the time period for
averaging the signal.
10
The averaging is a running
average.
EN 4.10 Version 2103