Installing block-type
current transformers or
voltage transformers
Connecting
high voltage cables
832-6063.0 * INSTALLATION SIMOSEC * REVISION 02
13.6

Connecting metering panel to high voltage

Fig. 51:
Cable connection in metering panel
For the exact panel dimensions, such as the cable connection height, please refer to the
dimension drawing and arrangement diagram of the switchgear.
Connect the voltage transformer's primary to the cable termination at the desired
point.
Check the tightening torque (37 lbf·ft or 50 Nm) of the bolted joint between the cable
and the block-type current and/or voltage transformers.
Bolt terminated cable to the cable connection terminal and avoid undue strain on
bushing. For the tightening torques of the cable lugs / cable terminations, please
observe the manufacturer's instructions, however do not exceed 37 lbf·ft (50 Nm).
Installation
a
Bus bar
s
4MA7 block-type
current transformer
d
Cable connection terminal
f
Bolted joint of cable
connection terminal and
cable lug
g
Cable termination
h
Grounding point of cable
shields (alternatively,
connect to ground bus bar)
j
Cold shrink insulation
(for over 15 kV )
k
Connection of voltage
transformer
l
Voltage transformer