832-6063.0 * INSTALLATION SIMOSEC * REVISION 02
Take the screwdriver out of the red/green plastic disc. Now check whether the
indicator shows the green area and the disc remains in this position. If the ready-for-
service indicator remains in this position (showing the green area), please check
whether the magnet is positioned at the mark.
Fig. 31:
Position of the ready-for-service indicator magnet
If the magnet is positioned exactly on the lower mark, the gas pressure is correct.
Fig. 32:
Magnet positioned on the lower mark
Fasten the front cover to close the front side of the panel.