832-6063.0 * MAINTENANCE SIMOSEC * REVISION 02
Verify that the grounding switch is closed, i.e., that the movable discharge switch
contacts are touching the lower fuse contacts - through the inspection window of
the cable compartment cover, or that the moving contacts of the switch-
disconnector are in the ''GRD" (''grounded") position.
Push interlocking lever upwards and hold in this position.
Fig 72:
Push interlocking lever upwards
Open the cable compartment door.
Fig 73:
Open cable compartment door
Release the interlocking lever.
Maintenance
93