Siemens SIMOSEC Operating Instructions Manual page 78

Medium voltage switchgear
Hide thumbs Also See for SIMOSEC:
Table of Contents

Advertisement

Operation
GROUNDED position in
fuse panel:
78
Insert operating lever (with red grip) onto operating shaft of operating mechanism.
Move operating lever down to the "GROUNDED" position.
Verify the position of the switch through the viewport.
Verify that the discharge switch is closed - i.e., the movable grounding contact
(option) is touching the second fuse contact - through the inspection window
of the cable compartment cover.
Position of discharging contacts with discharge switch in ''GROUNDED" position.
Remove operating lever.
Install padlock at center position of control gate of three-position switch (if desired).
Stow away operating lever.
The three-position switch is protected against unauthorized use, if the control gate is
padlocked.
REVISION 02 * OPERATION SIMOSEC* 832-6063.0