Installation
Checking the auxiliary
switch of the
ready-for-service
indicator
42
Checking the ready for service indicator
The auxiliary switch of the ready-for-service indicator can latch tight in the red area due to
extreme shocks during transport.
To put the ready-for-service indicator into operation again, the plastic part fixed at the
auxiliary switch must be brought to the initial position again by hand.
The following check can be carried out safely with the panel in operation.
Undo the four screws
a
a
Fig. 29:
SIMOSEC front
Insert the top of a screwdriver through the cutout of the red/green plastic disc.
Fig. 30:
Screwdriver in cutout of the red/green plastic disc
Push the small lever of the microswitch and keep it in this position, then turn the red/
green plastic disc carefully downwards until the pointer is in the green; keep this
position.
a
of the front cover and remove this front cover.
s
a
a
REVISION 02 * INSTALLATION SIMOSEC * 832-6063.0
a
Screws
s
Ready-for-service indicator