Installation
Bolting the panel to the
sill channels
Bolting the panel to the
foundation inserts
46
Align the panel in horizontal and vertical position.
Bolt the panel to the sill channels, without distorting the panel.
Drill holes for inserts according to the hole pattern (see dimension drawing).
Install the insert anchors.
Clean drilling dust and debris from the panel.
Align the panel in horizontal and vertical position.
Bolt the panel to the foundation inserts, without distorting the panel.
12.3

Aligning and joining another panel

For trouble-free operation, all panels must be in vertical position and may only have a
horizontal level difference (mis-alignment) of 0.04 in/yd (1 mm/m).
Establish the same level (0.04 in/yd (1 mm/m)) using shims
d
Align the panel
in horizontal and vertical position.
Fig. 36:
Alignment and levelling of panels
a
s
d
f
REVISION 02 * INSTALLATION SIMOSEC * 832-6063.0
f
.
Foundation
Aligned panel
Next panel
shims 0.02 - 0.04 in (0.5 - 1.0 mm)